INSP-Final Inspection | 12/2/2002 | 12/3/2002 | 12/3/2002 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/02/2002 at 11:27:31. Contact: ###-####.
|
INSP-Supply line flush | 11/15/2002 | 11/18/2002 | 11/18/2002 | A | PASS |
Rick Jackson
|
|
|
MICK PLEASE CALL 1 HR BEFORE SO THAT HE CAN MAKE SURE THAT HE IS READY; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
INSP-Final Inspection | 11/14/2002 | 11/15/2002 | 11/15/2002 | A | FAIL |
Troy Cobbley
|
|
|
underground supply from the street connection to the meter appears to be 1 1/4" . Per plan review comments it should be 2". The water meter appears to be 1" but review comments state its to be 2". The underground supply needs to be flushed per the review comments and the backflow preventer that is installed is not what was submitted. THE INSPECTION WAS STOPPED. NO OTHER ITEMS INSPECTED 11/15/2002 10:19:16 AM
|
INSP-Sprinkler Rough-in/Hydro | 9/12/2002 | 9/12/2002 | 9/12/2002 | P | PASS |
Rick Jackson
|
|
|
todd ; Phone #: ###-#### Internet Inspection Request from: Darla Downs hydro on overhead okay 9/12/2002 3:18:54 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/1/2002 | 8/1/2002 | 8/1/2002 | P | PASS |
Rick Jackson
|
|
|
okay to cover 8/1/2002 12:43:15 PM
|
INSP-Sprinkler Rough-in | 7/23/2002 | 7/23/2002 | 7/23/2002 | P | PART |
Rick Jackson
|
|
|
; Phone #: ###-#### plans are in the garage need nail plate at vertical pipe in main room; need tenting prior to covering ceiling; requested info on how they are going to have audible for flow alarm 7/23/2002 3:58:17 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/18/2002 | 7/19/2002 | 7/19/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 07/18/2002 at 15:32:52. Contact: ###-####. no plans 7/19/2002 4:54:06 PM
|