Permit Information
Permit NumberFIR02-00268
StatusVoid/No Violation
Name ADT SECURITY SERVICES, INC.
Site Address 900 W BOEING ST
Project Namealm-Boise Mobile Equipment
Customer Number 
ePlanReview 
Description
Boise Mobile Equipment - To install a new fire alarm system to provide offsite monitoring of the fire sprinkler system and monitoring of HVAC duct detectors for air handler shut down.
There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Conference6/7/20136/24/20136/24/2013ACANC
DetailsTroy Cobbley
Larry segreto ###-####
FIR-Aging Inspection6/3/20136/3/20136/7/2013 NR
DetailsTroy Cobbley
I stopped by the business and spoke with Larry Segreto, general manager, about this outstanding permit. He stated that he would follow up on it and that they also are working with Ray Criner about getting an occupancy permit. I told him that a final on the fire alarm permit would probably be required to get his occupancy. I set up a follow up conference.
FIR-Aging Inspection1/7/20131/7/20131/11/2013 FAIL
DetailsForrest France
FIR-Aging Inspection8/31/20128/31/20128/31/2012 DEFR
DetailsForrest France
FIR-Aging Inspection6/1/20126/1/20126/1/2012 DONE
DetailsForrest France
FIR-Aging Inspection12/6/201012/6/201012/8/2010 FAIL
DetailsForrest France
Ref. previous correction notice items.
FIR-Aging Inspection9/8/20109/8/20109/10/2010 FAIL
DetailsForrest France
INSP-Conference7/7/20107/7/20107/7/2010PDONE
DetailsTroy Cobbley
I went over the outstanding issues as per the permit history with Keith at ADT.
FIR-Aging Inspection6/21/20106/21/20106/23/2010 DONE
DetailsForrest France
INSP-Final Inspection1/9/20031/10/20031/10/2003PFAIL
DetailsTroy Cobbley
relocate smoke detector to more than 3' from the supply register and test, the smoke detector that was installed is not the smoke detector that was submitted. Provide approved smoke detector or resubmit new smoke detector information including compatibility listig to Sam Rogers for approval. This may require revised battery calcs. Duct detector in office area des not shut down HVAC unit when ativated, relocate duct detector in shop area out of the 90 degree bend and test, pressure switch on the sprinkler riser did not send signal to the FACP , test tamper switch, install electric alarm bell, provide a map per review note #4, rovide signs on the FACP door and the fire sprinkler riser door per note #12 1/10/2003 3:36:22 PM
FIR-Aging Inspection1/6/20031/6/20031/6/2003 NR
DetailsRick Jackson
talked to Matt and he said he would get with Debest and will schedule a test 1/6/2003 9:36:16 AM