INSP-Final Inspection | 1/28/2003 | 1/31/2003 | 1/31/2003 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 1/28/2003 at 4:30:45 PM. Contact: ###-####.
|
INSP-Final Inspection | 11/21/2002 | 11/22/2002 | 11/22/2002 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 11/21/2002 at 08:38:37. Contact: ###-####. relocate AV to within 15 ft of corridor; recalc NAC's; gym overspaced for strobe placement; need knox box and map at panel; NAC's not temporal; need to test inittiating and av equipment in out buildings 11/22/2002 5:18:43 PM
|
INSP-Final Inspection | 11/5/2002 | 11/8/2002 | 11/8/2002 | P | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 11/05/2002 at 11:46:46. Contact: . received call from Mike Wyatt that they weren't ready; will try again next week 11/8/2002 4:23:42 PM
|