Permit Number | FIR02-00302 |
Status | Finaled |
Name |
MICRON TECHNOLOGY INC
|
Site Address |
8000 S FEDERAL WAY
|
Project Name | ALM-MICRON B21 Server Room, PC |
Customer Number | 4849 |
ePlanReview | |
Description |
MICRON B21 Server Room, PCS4849 - To replace existing alarm devices with new a/v devices, to meet current code; to add a duct smoke detector for HVAC air handler shut down; and to also monitor a voluntary Vesda smoke detection system serving the project area, via alarm and trouble connections to the existing building fire alarm system.
NOTE: This permit does not include approval of the Vesda system itself, because there are no UFC requirements for this system; insufficient information is included in this submittal to verify the design of the system, and it does not impact on the performance of the required building alarm system.
There is no associated building permit.
|