Permit Information
Permit NumberFIR02-00338
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1666 W COMMERCE AVE
Project NameSPR FIRE STATION #7
Customer Number 
ePlanReview 
Description
Fire Station #7 * To install a complete fire sprinkler protection, incorporating wet and dry pipe systems, designed for both Light and Ordinary Group 2 hazard occupancies in an existing, 17,620 ft/2 pre-engineered remodeled type V-N building, and a new 2,500 ft/2 second story addition. This permit includes a 6" C-900 underground fire service supply main which taps to an 8" existing supply in Commerce Street, running north approximately 55'-0" into the south west corner of this same existing structure. This facility will house a fire station. The Fire Department will occupy the entire building and rooms with unidentified uses under this permit are declared S-1 storage and require OH-2 fire sprinkler area/density protection. The second floor will house the living quarters for the Fire Fighters. All fire sprinkler system installation work and equipment, materials and appurtenance shall comply with NFPA 13?1999, 24-1995, 72-1999, attached review comment and conditions list; as regulated by the Fire Chief. These notes, permit and fire Inspection Card are required to be on site as a condition of this work, to provide witness of compliance verification meeting minimum code. This permit is attached to building permit BLD01-03095.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/27/20032/27/20032/27/2003PPASS
DetailsRick Jackson
INSP-Sprinkler Rough-in2/19/20032/20/20032/20/2003APASS
DetailsRick Jackson
43 psi air test okay on dry air test 2/20/2003 9:39:42 AM
INSP-Sprinkler Rough-in/Hydro2/18/20032/19/20032/19/2003APART
DetailsRick Jackson
doug; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie started 24 hr air test at 43 psi. 2/19/2003 10:27:25 AM
INSP-Sprinkler Rough-in/Hydro2/13/20032/14/20032/14/2003AFAIL
DetailsRick Jackson
###-#### complete 24 hr air test fail - pressure down to 35 psi 2/14/2003 9:04:35 AM
INSP-Sprinkler Rough-in/Hydro2/12/20032/13/20032/13/2003APART
DetailsRick Jackson
###-#### eric started 24 hr test - pressure at 41 psi'; will return tomorrow at 10 am 2/13/2003 11:06:22 AM
INSP-Sprinkler Rough-in/Hydro1/9/20031/9/20031/9/2003PPART
DetailsRick Jackson
above grnd. ###-#### above ground hydro okay 1/9/2003 1:17:06 PM
INSP-Sprinkler Rough-in/Hydro1/7/20031/7/20031/7/2003PFAIL
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung partial r/i as not all heads are completed; need high temp head at heater in west bay; heads obstructed by cabinets in 2 sleeping rooms on south side; main missing hanger in west bay; need head in electrical room; need drum drip on inspectors test 1/7/2003 11:33:05 AM
INSP-Sprinkler Rough-in/Hydro1/7/20031/7/20031/7/2003APART
DetailsRick Jackson
UG hydro okay
INSP-Supply line flush11/13/200211/14/200211/14/2002APASS
DetailsTroy Cobbley
james; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
INSP-Sprinkler Rough-in/Hydro11/4/200211/5/200211/5/2002AFAIL
DetailsRick Jackson
###-#### james need to get heads closer to deck with sprigs on east hall by stalls prior to covering (obstructions by duct, etc.) 11/5/2002 11:37:37 AM
INSP-Sprinkler Rough-in10/16/200210/17/200210/17/2002PPART
DetailsRick Jackson
###-#### second floor okay to cover 10/17/2002 4:44:52 PM
INSP-Supply line flush9/6/20029/9/20029/9/2002PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 09/06/2002 at 15:27:23. Contact: ###-####. not flush; cover inspection for the underground only - okay to cover, 6 inch ran from building to property line 9/9/2002 4:00:40 PM