INSP-Final Inspection | 4/25/2003 | 4/25/2003 | 4/25/2003 | A | PASS |
Troy Cobbley
|
|
|
Phase 1 fire sprinklers finaled.
|
INSP-Final Inspection | 4/22/2003 | 4/23/2003 | 4/23/2003 | P | FAIL |
Troy Cobbley
|
|
|
Remove batt insulation in attic space over the maint. shop, provide map for fire alarm system, upright sprinkler heads in the attic space over the maint. shop appear to be blocked by truss panels 4/23/2003 3:34:31 PM
|
INSP-Sprinkler Rough-in/Hydro | 4/22/2003 | 4/23/2003 | 4/23/2003 | P | PASS |
Troy Cobbley
|
|
|
need to complete air test; 40.5 psi and cooler at -22 degrees F. Air test is OK 4/23/2003 3:31:15 PM
|
INSP-Sprinkler Rough-in/Hydro | 4/22/2003 | 4/22/2003 | 4/22/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 4/22/2003 at 6:42:45 AM. Contact: ###-####. stated 24 hr air test; 40.5 psi and freezer is at -22 degrees F. 4/22/2003 1:08:24 PM
|
INSP-Sprinkler Rough-in/Hydro | 3/27/2003 | 3/28/2003 | 3/28/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/27/2003 at 5:19:52 PM. Contact: ###-####. forward flow of BFP okay; hydro on old wet system okay 3/28/2003 3:31:00 PM
|
INSP-Sprinkler Rough-in/Hydro | 3/19/2003 | 3/20/2003 | 3/20/2003 | A | PART |
Rick Jackson
|
|
|
RUSS; Phone #: ###-#### Internet Inspection Request from: Annette Moore hydro okay on all piping in pump room 3/20/2003 11:09:56 AM
|
INSP-Conference | 3/17/2003 | 3/19/2003 | 3/19/2003 | A | PASS |
Troy Cobbley
|
|
|
above ground hydro test for the pre-action system in the freezer is ok. The system was tested from the control valve at base of riser 3/19/2003 2:25:11 PM
|
INSP-Sprinkler Rough-in | 3/17/2003 | 3/18/2003 | 3/18/2003 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was for the 24 hour air test. Test was a fail due to freezer not being at the lowest nominal level. See NFPA 10-2.3.1 3/18/2003 3:59:33 PM
|
INSP-Conference | 3/11/2003 | 3/13/2003 | 3/13/2003 | P | PART |
Troy Cobbley
|
|
|
Inspection was for the testing of the fire pump. Russ with Nickerson pump was present to perform the test 3/13/2003 3:26:55 PM
|
INSP-Supply line flush | 3/7/2003 | 3/10/2003 | 3/10/2003 | P | PASS |
Troy Cobbley
|
|
|
underground hydro and flush ok 3/10/2003 3:40:18 PM
|
INSP-Supply line flush | 3/5/2003 | 3/7/2003 | 3/7/2003 | A | FAIL |
Troy Cobbley
|
|
|
The contractor is not getting enough flow for a flush due to 300' of hose. A minimum 880 gallons is required. Flush to be rescheduled 3/7/2003 11:21:48 AM
|
INSP-Conference | 12/23/2002 | 12/24/2002 | 12/24/2002 | A | DONE |
Troy Cobbley
|
|
|
spoke with the fire sprinkler and the general contractors about the pre-action fire sprinkler system 12/24/2002 10:02:19 AM
|
INSP-Conference | 12/20/2002 | 12/20/2002 | 12/20/2002 | P | CANC |
Troy Cobbley
|
|
|
cancelled by Jeff with Treasure Valley Fire 12/20/2002 3:42:45 PM
|
INSP-Conference | 12/11/2002 | 12/11/2002 | 12/11/2002 | P | PART |
Troy Cobbley
|
|
|
all underground is ok to cover except for the section that will tie to the united water stub-in 12/11/2002 3:51:27 PM
|
INSP-Conference | 12/10/2002 | 12/10/2002 | 12/10/2002 | P | PART |
Troy Cobbley
|
|
|
the remaining section of piping from the new riser to the pump room is OK to bury. 12/10/2002 4:08:19 PM
|
INSP-Conference | 12/9/2002 | 12/9/2002 | 12/9/2002 | P | PART |
Troy Cobbley
|
|
|
the inspection was from the north stub-in to the first 90 elbow and then three additional lenghts of pipe. This section of the underground I witnesses the bedding and the covering as well as the pipe being installed. It was OK to cover. The rest of the pipe will be inspected later 12/9/2002 4:24:20 PM
|