Permit Information
Permit NumberFIR02-00406
StatusFinaled
Name TREASURE VALLEY COFFEE INC
Site Address 11875 W PRESIDENT DR
Project NameSPR Treasure Valley Coffee
Customer Number 
ePlanReview 
Description
Treasure Valley Coffee * To extend fire sprinkler protection using special designed system for the 2,580 ft/2 addition of a Type V-N, one story covered structure which is fully fire sprinklered. This is an open steel structure with pre-finished metal roof and pre-finished metal 1hr exterior wall along the east property line. Fire sprinklers used for area increase. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-01350.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/5/20032/5/20032/5/2003PPASS
DetailsTroy Cobbley
JEFF; Phone #: ###-#### Internet Inspection Request from: Darla Downs
INSP-Final Inspection2/3/20032/3/20032/3/2003PFAIL
DetailsTroy Cobbley
After a on site inspection and conversing with Bill Alexander the items stored under the new canopy appear to exceed the classifications the sprinkler system was designed to. The contractor will need to resubmitt information to verify the system is per code. A storage rack has been installed and will require a racking permit before use. 2/3/2003 2:43:44 PM
INSP-Sprinkler Rough-in/Hydro12/4/200212/4/200212/4/2002PFAIL
DetailsTroy Cobbley
sprinkler piping hydro test is ok. sprinkler piping rough-in is ok. control valve needs to be connected to the existing fire alarm panel and anti-freeze needs to be installed. Drawings will need to be submitted 12/4/2002 3:16:03 PM 12/4/2002 3:17:43 PM