Permit NumberFIR02-00454
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 190 E BANNOCK ST
Project NameSPR ST. LUKES PHASE 2
Customer Number 
ePlanReview 
Description
(PHASE II - St. Lukes RMC Fire Code Upgrade) To install the remaining separate 6" supply feed mains in the basement and up through the stair towers for the separation/connection of high-pressure supplies to the stair well # 6, and 7, North Wing Tower. This includes the new mains and reconnection of sprinkler risers that would be on the high-pressure system piping, reconnection to the low pressure piping from the 3rd floors to the 6th. (The top floor may change due to future testing verification of which changes must be documented). Reference attached plans. This work is to reduce excessive (+175 lbs) pressure created by a previous installation/replaced fire booster pump with a 1000gpm @ 115lb rated fire booster pump (for the East Wing Tower Expansion, under the auspices of the State Fire Marshall's Office). The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, plans, permit and fire "Inspection Card" are required to be on site as a condition of this work, for witness of compliance verification of minimum code. This permit is not attached to a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/23/20034/23/20034/23/2003PPASS
DetailsRick Jackson
INSP-Final Inspection3/24/20034/2/20034/2/2003PPART
DetailsRick Jackson
1 pm ###-#### completed flow test of standpipe on 10th floor - 2.5 inch orifice with 9 psi pitot and 109 psi residual - acceptable and awaiting basement plan per Bill Alexander 4/2/2003 3:23:39 PM
INSP-Sprinkler Rough-in3/10/20033/12/20033/12/2003APART
DetailsRick Jackson
brad; Phone #: ###-#### Internet Inspection Request from: Annette Moore hydro okay on low pressure side 3/12/2003 1:02:36 PM
FIR-Aging Inspection3/6/20033/6/20033/6/2003 NR
DetailsRick Jackson
work is still in progress and resubmittals are coming per e-mail from Bill Alexander 3/6/2003 1:03:41 PM