Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR02-00478
StatusFinaled
Name THE SECURITY GROUP
Site Address 12601 W EXPLORER DR
Project Namealm-Brighton Plaza
Customer Number 
ePlanReview 
Description
Brighton Plaza Office Shell & Core - To install a fire alarm system in a new building. The system will include monitoring of fire sprinklers, smoke and heat detection for elevator recall and shunt trip, and monitoring of duct detectors for HVAC air handler shut down.
The associated building permit (BLD 01-02706) is to construct a two story,type VN, fully fire sprinklered 41,472 sq. ft. shell and core office building with site improvements. Area of first floor is 20,559 sq. ft. with second floor 20,913 sq. ft. Fire sprinklers used for area increase. No occupancy is allowed under this permit. Separate plans and permits shall be required for each tenant space.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/18/20038/18/20038/18/2003PPASS
DetailsTroy Cobbley
INSP-Alarm Testing4/8/20034/9/20034/9/2003PPART
DetailsTroy Cobbley
duct smoke detectors tested out OK 4/9/2003 4:02:21 PM
INSP-Alarm Testing4/7/20034/8/20034/8/2003PCANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 4/7/2003 at 1:38:39 PM. Contact: ###-####. Security Group called and said they will reschedule for 4/9/03 4/8/2003 1:44:31 PM
INSP-Alarm Testing4/4/20034/7/20034/7/2003PPART
DetailsTroy Cobbley
elevator recall is ok 4/7/2003 3:46:22 PM
INSP-Final Inspection3/27/20033/31/20033/31/2003AFAIL
DetailsTroy Cobbley
MIKE 8AM INSPECTION; Phone #: ###-#### test all recall functions for the elevator including all heat and smoke detectors, provide smoke for all fire smoke dampers per review note #6, provide duct smoke detectors on the supply side of the HVAC units or get permission from the boise fire dept. to leave them on the return side, provide a map of system 3/31/2003 9:40:44 AM
FIR-Aging Inspection3/18/20033/18/20033/18/2003 NR
DetailsTroy Cobbley
Mike with the Security Group left a message on my voice mail stating that an inspection would be called in later this week 3/19/2003 7:55:05 AM