Permit Number | FIR02-00480 |
Status | Finaled |
Name |
SIMPLEX/GRINNELL
|
Site Address |
3201 W AIRPORT WAY
|
Project Name | alm - AIRPORT-NEW TERMINAL |
Customer Number | |
ePlanReview | |
Description |
BOISE CITY AIRPORT /Temp elevated walkways modification - To install a temporary addressable, fire alarm control panel to serve the required fire alarm devices within a portion of the temporary elevated walkways. The system will include sprinkler waterflow and valve tamper monitoring, manual pull stations, horn/strobes, smoke detection for HVAC air handler shut down and release of smoke rated door hold-opens, and a remote annunciator. The panel will be interconnected in a Listed manner with the existing airport fire alarm system for "alarm" signals only. Supervisory and trouble signals will be annunciated locally only, at the 2nd floor Operations Center. Final approval of this permit shall be contingent upon formal approval by the Building Department and Fire Department of the proposed construction modifications and use of the walkways, which are to be to be submitted as modifications to building permit BLD 02-03428.
|