Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR02-00500
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 8211 W USTICK RD
Project NameALM-Capitol Care Facility
Customer Number 
ePlanReview 
Description
Capitol Care Facility - To replace the existing fire alarm panel and install new fire alarm devices within the entry lounge, offices and Nurse's station, in accordance with Phase 1 of a programmed fire alarm upgrade agreement, approved 1/9/02 by the Boise City Fire Dept. The project includes a new 4100U fire alarm panel, to be networked to the existing 4020 FAC panel in the adjacent building, and a new NAC extender panel to power the existing bell devices, which are to be replaced under subsequent phases of the upgrade. Coverage includes manual pulls, area smoke detection, sprinkler system monitoring, and a/v notification appliances.
There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/13/20036/16/20036/16/2003AFAIL
DetailsTroy Cobbley
The map provided does not show exact initiating device location or address. Provide correct address 6/16/2003 11:35:08 AM
INSP-Final Inspection6/16/20036/16/20036/16/2003APASS
DetailsTroy Cobbley
Map and signs provied
INSP-Final Inspection6/6/20036/10/20036/10/2003AFAIL
DetailsTroy Cobbley
provide signs on the riser room and fire alarm room doors and provide maps for initiating devices and facp location at the nurses station 6/10/2003 10:37:10 AM
FIR-Aging Inspection5/14/20035/14/20035/14/2003 NR
DetailsTroy Cobbley
Work in progress per Robert Spinden with SimplexGrinnell. He stated that the project was about complete and that the final inspection was not far off. 5/15/2003 1:48:44 PM