Permit NumberFIR03-00009
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 102 N COLE RD
Project NameSPR BUDGET OFFICE FURNITURE
Customer Number 
ePlanReview 
Description
(BUDGET OFFICE FURNITURE - SKATEWORLD BLDG) To remodel a 22,501 ft/2 roller skating rink to convert to a retail/warehouse office furniture tenant per approved plans on file. Fire sprinkler work is related to the construction of interior partitions to create new office area, three new restrooms, and tenant demising wall, the installation of new truck ramp and the installation of suspended ceiling system in office areas. All work related and addressed in this permit shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of meeting minimum code. This permit is attached to a building demo permit: BLD02-02924.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro3/21/20033/21/20033/21/2003PPASS
DetailsTroy Cobbley
dutch; Phone #: ###-#### Fire sprinklers finaled 3/21/2003 4:34:21 PM
INSP-Final Inspection3/4/20033/4/20033/4/2003PFAIL
DetailsTroy Cobbley
Remove wrapping form the upright heads in the bail bonds tenant, test the sprinkler monitoring devices, provide signage for the inspectors test valve and control valve per review note #66 and #56, provide inspection tag pre review note #67, provide sign on the bell per review note #68, provide forward flow test per review note #73, provide test papers for the hydro test per review note #69, provide sidewall sprinkler head under the overhead door per review note #62 and plans, provide relief vavle on riser per review note #52, sprinkler pendant in the womens restroom is to close to the register. comply with review note #48. Above ground hydro test is OK 3/4/2003 4:35:40 PM 3/4/2003 4:36:10 PM