Permit Information
Permit NumberFIR03-00114
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 405 E HIGHLAND VIEW DR
Project NameSPR GOUL ASHLEY-HILLSIDE
Customer Number 
ePlanReview 
Description
To construct a 2,282-ft/2 one story single family dwelling with a 941-ft/2 unfinished basement, a 936 sq. ft. four car garage/mechanical room per approved plans, all engineering/red-lining and attached requirement lists. This lot is within a hillside area and is subject to the hillside ordinances. The sprinkler flow alarm shall be attached to the residence smoke detection system. Separate permits may be required to finish basement. This structure requires the installation of a NFPA 13D fire sprinkler system. All fire sprinkler work and related (which includes dual service water supply, backflow prevention (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review notes, as regulated by the Fire Department. This permit is attached to: BLD02-02864.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/14/20035/14/20035/14/2003PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 5/14/2003 at 11:09:18 AM.
INSP-Final Inspection5/13/20035/13/20035/13/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 5/13/2003 at 8:15:00 AM. Contact: ###-####. no provisions for inspectors test to drain outside - owner wants hose bib to run outside; main shut off after domestic shutoff is to be removed 5/13/2003 1:20:39 PM
INSP-Final Inspection5/9/20035/9/20035/12/2003PNH
DetailsRick Jackson
Scheduled by a contractor via Hello! on 5/9/2003 at 10:36:49 AM. Contact: ###-####. OWNER NOT HOME 5/12/2003 8:56:23 AM
INSP-Final Inspection5/7/20035/8/20035/8/2003ANR
DetailsRick Jackson
Scheduled by a contractor via Hello! on 5/7/2003 at 1:32:25 PM. Contact: ###-####. need to test the water flow alarms; tlaked to Jim Danes and he will reschedule 5/8/2003 10:16:12 AM
INSP-Sprinkler Rough-in/Hydro4/3/20034/4/20034/4/2003APART
DetailsTroy Cobbley
pendant drop in cellar exceeds 9' off of wall and 1" armover in basement needs hanger since its over 2' long 4/4/2003 11:10:45 AM
INSP-Sprinkler Rough-in/Hydro4/2/20034/3/20034/3/2003AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 4/2/2003 at 7:21:37 AM. Contact: ###-####. need plans; need nail plates where vertical CPVC passes through stud cavity; deflector bent (under stairs) 4/3/2003 8:53:16 AM