INSP-Final Inspection | 2/24/2004 | 2/24/2004 | 2/24/2004 | P | PASS |
Rick Jackson
|
|
|
We would like a final this PM. Please
call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|
INSP-Final Inspection | 2/24/2004 | 2/24/2004 | 2/24/2004 | P | PASS |
Rick Jackson
|
|
|
We would like a final this PM. Please
call prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|
INSP-Final Inspection | 2/19/2004 | 2/20/2004 | 2/20/2004 | A | FAIL |
Rick Jackson
|
|
|
Call Mike prior to arrival; Phone #: ###-#### Internet Inspection Request from: Trent Bice need all trim completed 2/20/2004 4:26:57 PM
|
INSP-Sprinkler Rough-in/Hydro | 2/10/2004 | 2/11/2004 | 2/11/2004 | A | PART |
Rick Jackson
|
|
|
hydro okay 2/11/2004 11:38:34 AM
|
INSP-Sprinkler Rough-in/Hydro | 2/6/2004 | 2/10/2004 | 2/10/2004 | A | FAIL |
Rick Jackson
|
|
|
Scott Carter 4 of 6; Phone #: ###-#### Internet Inspection Request from: Trent Bice 2nd and 6th floors not holding pressure 2/10/2004 3:57:11 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:42:50 PM. Contact: ###-####. hydro on standpipe okay 10/28/2003 1:00:35 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/16/2003 | 10/17/2003 | 10/17/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/16/2003 at 4:09:05 PM. Contact: ###-####. okay to cover 5-6 floors; firestopping needed at corridor 10/17/2003 10:22:17 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/15/2003 | 10/16/2003 | 10/16/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/15/2003 at 12:57:27 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:56:35 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:55:42 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:54:45 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/15/2003 at 12:53:42 PM. Contact: ###-####. straps needed 628/609/room for construction elevator; elevator machine room requires SR heads - not QR 10/16/2003 4:03:27 PM 10/16/2003 4:04:31 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/14/2003 | 10/15/2003 | 10/15/2003 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/14/2003 at 11:39:44 AM. Contact: ###-####. okay to cover rooms; fire stopping needed in corridor 10/15/2003 11:12:02 AM
|
INSP-Sprinkler Rough-in/Hydro | 9/10/2003 | 9/11/2003 | 9/11/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/10/2003 at 8:38:12 AM. Contact: ###-####. okay to cover rooms; corridor requires firestopping; standpipes over 48 inches high 9/11/2003 12:34:23 PM
|
INSP-Sprinkler Rough-in | 9/4/2003 | 9/4/2003 | 9/4/2003 | A | PART |
Rick Jackson
|
|
|
okay to cover rooms; corridor pipe not restrained to prevent upward movement; fire stopping required in corridor 9/4/2003 8:57:40 AM
|
INSP-Sprinkler Rough-in/Hydro | 8/29/2003 | 9/2/2003 | 9/2/2003 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 8/29/2003 at 11:39:03 AM. Contact: ###-####. Scheduled by a contractor via Hello! on 8/29/2003 at 11:37:39 AM. Contact: ###-####. Scheduled by a contractor via Hello! on 8/29/2003 at 11:36:25 AM. Contact: ###-####. Scheduled by a contractor via Hello! on 8/29/2003 at 11:31:17 AM. Contact: ###-####. Scheduled by a contractor via Hello! on 8/29/2003 at 11:29:53 AM. Contact: ###-####. Scheduled by a contractor via Hello! on 8/29/2003 at 11:40:27 AM. Contact: ###-####. corridor heads have too much vertical movement; rooms 304 and 302 need straps; 318 has excessive bend in pipe and may leak; 306 has head that is rotated 9/2/2003 3:39:22 PM
|
INSP-Sprinkler Rough-in | 8/27/2003 | 8/28/2003 | 8/28/2003 | A | PART |
Rick Jackson
|
|
|
pipe in corridors has excessive upward movement - need to restrain; rooms okay to cover on second floor only 8/28/2003 11:04:10 AM 8/28/2003 11:05:16 AM
|
INSP-Sprinkler Rough-in/Hydro | 8/26/2003 | 8/27/2003 | 8/27/2003 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 8/26/2003 at 8:46:54 AM. Contact: ###-####.
|
FIR-Aging Inspection | 7/3/2003 | 7/3/2003 | 7/3/2003 | | PASS |
Rick Jackson
|
|
|
this project is still under construction and in progress 7/3/2003 9:40:16 AM
|