Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR03-00177
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 10172 W SMOKE RANCH DR
Project NameSPR Alzheimers Care Facility
Customer Number 
ePlanReview 
Description
FIR03-00177 - Area #3 * To construct a one story Type V1hr fully fire sprinklered care facility to include the south side only with 17 sleeping rooms, laundry, storage per approved plans and attachments. Fire sprinklers used for area increase. The fire sprinkler system work shall be installed in accordance to NFPA 13-1999, complying with the UFC-1997 and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground supply installation permit is FIR03-00112. This permit is attached to garage shell permit: BLD02-002474.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/4/20039/4/20039/4/2003PPASS
DetailsTroy Cobbley
fire sprinklers finaled
INSP-Sprinkler Rough-in/Hydro6/24/20036/24/20036/24/2003PPASS
DetailsTroy Cobbley
24 hour air test on the dry system passed 6/24/2003 4:44:51 PM
INSP-Sprinkler Rough-in/Hydro6/24/20036/24/20036/24/2003PFAIL
DetailsTroy Cobbley
pressure test on the wet system failed
INSP-Sprinkler Rough-in/Hydro5/28/20035/29/20035/29/2003APASS
DetailsTroy Cobbley
cameron; Phone #: ###-#### Sprinkler piping is ok in the south wing. Insulation still missing on the plastic piping in places. I called cameron and left message not to cover pipe until I had reinspected it. 5/29/2003 8:51:04 AM