Permit NumberFIR03-00193
StatusFinaled
Name ALARMCO
Site Address 3749 N CLOVERDALE RD
Project NamealmASHLEY MANOR CARE CNTRS INC
Customer Number 
ePlanReview 
Description
To provide one duct detector for HVAC shutdown, one magnetic door hold open and one smoke detector to release the door hold open, all devices connected to the existing fire alarm system. No off site monitoring is provided or required.
The associated building permit (BLD 02-00242) is to increase the patient bed capacity of an existing R-3 congregate care facility that was previously approved by Ada County to 10 beds. Additional work included in this permit is to inspect and approve an existing garage conversion to office space and make code compliant with accessible restrooms and an occupancy separation wall. All construction per the approved plans, attached comment list and the structural inspector's requirements. NOTE: The care facility is fire sprinklered per NFPA 13-R, which was required by the State of Idaho.

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/26/20036/27/20036/27/2003APASS
DetailsTroy Cobbley
###-#### Life safety finaled 6/27/2003 10:55:30 AM
INSP-Final Inspection6/20/20036/20/20036/20/2003PPASS
DetailsTroy Cobbley
fire alarm finaled. Zone 3 on the fire alarm panel failed. Wires were transfered to zone 5 which was a spare. The owner was notified 6/20/2003 12:51:54 PM
INSP-Final Inspection6/18/20036/19/20036/19/2003PFAIL
DetailsTroy Cobbley
The batteries supplied aren't large enough for the system. The measured current draw was 560 milli amp, which means 16.128 ah batteries are required. 7 ah batteries are installed and per the manufacturers paperwork 12 ah is the largest that can be supported by the panel. Label dedicated circuit breaker and provide lock for it 6/19/2003 2:19:23 PM
INSP-Final Inspection6/12/20036/16/20036/16/2003PFAIL
DetailsTroy Cobbley
relocate smoke detector to with in 5' of the door and test. Provie map at facp. Provide sign on door. Test the duct smoke detector and test current draw of the panel for battery size verification 6/16/2003 3:10:38 PM