INSP-Final Inspection | 6/26/2003 | 6/27/2003 | 6/27/2003 | A | PASS |
Troy Cobbley
|
|
|
###-#### Life safety finaled 6/27/2003 10:55:30 AM
|
INSP-Final Inspection | 6/20/2003 | 6/20/2003 | 6/20/2003 | P | PASS |
Troy Cobbley
|
|
|
fire alarm finaled. Zone 3 on the fire alarm panel failed. Wires were transfered to zone 5 which was a spare. The owner was notified 6/20/2003 12:51:54 PM
|
INSP-Final Inspection | 6/18/2003 | 6/19/2003 | 6/19/2003 | P | FAIL |
Troy Cobbley
|
|
|
The batteries supplied aren't large enough for the system. The measured current draw was 560 milli amp, which means 16.128 ah batteries are required. 7 ah batteries are installed and per the manufacturers paperwork 12 ah is the largest that can be supported by the panel. Label dedicated circuit breaker and provide lock for it 6/19/2003 2:19:23 PM
|
INSP-Final Inspection | 6/12/2003 | 6/16/2003 | 6/16/2003 | P | FAIL |
Troy Cobbley
|
|
|
relocate smoke detector to with in 5' of the door and test. Provie map at facp. Provide sign on door. Test the duct smoke detector and test current draw of the panel for battery size verification 6/16/2003 3:10:38 PM
|