Permit Information
Permit NumberFIR03-00206
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 7960 W NORTHVIEW ST
Project NameSPR St Marks Catholic Communit
Customer Number 
ePlanReview 
Description
(Building Area "B" New Church) * To install a fire sprinkler protection in a new 26,050-ft/2 single story, sanctuary, restroom and entry vestibule. Work is to also remove and cap and relocate the wet riser in Building "A" to a new location in Building "B". This building is fully fire sprinklered for one-hour substitution. Sprinkler demolition (entry) permit associated with this permit is: FIR03-00168. Underground service supply main is permitted under: FIR03-00035. Fire sprinkler work shall be in accordance to NFPA 13-1999, complying with the IFC-2000 and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to Building Permit: BLD02-02454.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/21/20041/21/20041/21/2004APASS
DetailsTroy Cobbley
INSP-Final Inspection1/12/20041/13/20041/13/2004AFAIL
DetailsTroy Cobbley
Project not ready for final inspection yet. Inspection was for covering the sprinklers in the remodeled existing area. Sprinklers are OK to cover 1/13/2004 9:33:07 AM
INSP-Final Inspection12/22/200312/23/200312/23/2003APART
DetailsTroy Cobbley
A temporary occupancy was given with dave millers permission for use of the new church pending the completion of the existing church areas 12/23/2003 8:39:13 AM
INSP-Sprinkler Rough-in/Hydro12/19/200312/22/200312/22/2003APASS
DetailsTroy Cobbley
Overhead sprinkler system hydro test is ok 12/22/2003 12:39:00 PM
INSP-Conference12/19/200312/19/200312/19/2003PDONE
DetailsTroy Cobbley
Spoke with sprinkler contractor about a temporary occupancy 12/19/2003 1:37:19 PM
INSP-Sprinkler Rough-in12/10/200312/10/200312/10/2003PPART
DetailsTroy Cobbley
See approved plans for areas with todays date that are ok to cover 12/10/2003 12:47:55 PM
INSP-Sprinkler Rough-in/Hydro11/17/200311/17/200311/17/2003PPART
DetailsTroy Cobbley
the two uprights and two pendants in the connecting area are ok to cover. I notified Gerald with Treasure Valley Fire that it looks like a upright head will be required in the mechanical chase unless they can meet exception 12 of concealed combustible spaces 11/17/2003 2:19:27 PM
INSP-Sprinkler Rough-in/Hydro11/3/200311/3/200311/3/2003PPART
DetailsTroy Cobbley
sprinklers are ok to cover in the round chapel area in the connection between the new church and the existing area 11/3/2003 2:42:22 PM
INSP-Sprinkler Rough-in9/25/20039/25/20039/25/2003PPART
DetailsTroy Cobbley
The prayer sanctuary sprinkler piping is ok to cover 9/25/2003 2:57:07 PM
INSP-Sprinkler Rough-in9/12/20039/12/20039/12/2003PPART
DetailsTroy Cobbley
south half of sanctuary is ok to cover 9/12/2003 2:56:52 PM
INSP-Sprinkler Rough-in9/9/20039/9/20039/9/2003PPART
DetailsTroy Cobbley
###-#### mike The high vaulted ceiling in the sanctuary area, the high ceiling area to the immediate north and the lower soffit area to the north is ok to cover 9/9/2003 2:00:00 PM 9/9/2003 2:01:35 PM
INSP-Sprinkler Rough-in8/18/20038/19/20038/19/2003PPART
DetailsTroy Cobbley
See approved job site plans for areas with deficencies 8/19/2003 4:10:12 PM
INSP-Sprinkler Rough-in8/18/20038/18/20038/18/2003PPART
DetailsTroy Cobbley
MIKE ###-#### I looked at the piping in the high ceiling area that runs east/west and it is ok to cover. The piping as installed in the high ceiling areas that run north/south do not match plans and need to be resubmitted 8/18/2003 4:20:18 PM