Permit Information
Permit NumberFIR03-00209
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 12601 W EXPLORER DR Unit: 250
Project NameSPR ZASIO BRIGHTON PL-2ND FLR
Customer Number 
ePlanReview 
Description
(ZASIO - SUITE 250) To install fire sprinkler protection in a new 8,842-ft/2 office tenant within a shell portion of a structure comprising of space located on the 22,000 square foot 2nd floor of a 44,000 square foot, 2 story, building. Fire sprinkler work is related to tenant demising walls, a restroom, interior nonbearing walls and suspended ceilings all per approved drawings and plan review conditions on file. This building is fire sprinklered for building area increase. The fire sprinkler system work shall be installed in accordance to NFPA 13-1999, complying with the IFC-2000 and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-02987.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/22/20038/22/20038/22/2003PPASS
DetailsTroy Cobbley
INSP-Final Inspection8/4/20038/5/20038/5/2003AFAIL
DetailsTroy Cobbley
replace painted pendant in the restroom on the 2nd floor, provide missing canopies, provide tile in the comm. room, provide ceiling in the sky light area, provide tags for riser and backflow preventer, provide knox key box, provide forward flush for the backflow preventor, test all sprinkler devices 8/5/2003 1:08:14 PM
INSP-Sprinkler Rough-in6/2/20036/2/20036/2/2003PPART
DetailsTroy Cobbley
Ok to cover piping over the hard lid areas. Add one pendant in closet marked on the approved plans 6/2/2003 3:51:17 PM