Permit Information
Permit NumberFIR03-00214
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 3323 N LAKEHARBOR LN
Project NameSPR SILVER LAKE APARTMENTS
Customer Number 
ePlanReview 
Description
(SILVER LAKE APARTMENTS Building "B") - To install a NFPA 13R fire sprinkler system in a new 16,416-ft/2, three story, wood framed, 18 unit apartment building. The first floor is 7,506-ft/2. The second floor is 7,080ft/2, and the third floor is 1,830-ft/2. This permit includes approximately 180'-0" of 4" C-900 underground pipe form the property line at Lake Harbor into a small fire sprinkler control room on the S.W. corner of the building. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-01157.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/25/20046/25/20046/25/2004APASS
DetailsRick Jackson
INSP-Final Inspection5/28/20046/1/20046/1/2004PFAIL
DetailsRick Jackson
bob erland; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Need NFPA 25 6/1/2004 3:59:30 PM
INSP-Final Inspection5/27/20045/27/20045/27/2004PFAIL
DetailsTroy Cobbley
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry.
FIR-Aging Inspection3/12/20043/12/20043/12/2004PPASS
DetailsTroy Cobbley
underground flush ok 3/12/2004 4:29:01 PM
INSP-Supply line flush3/11/20043/11/20043/11/2004PCANC
DetailsTroy Cobbley
United water could not find the water valve to turn on underground water supply 3/11/2004 3:36:47 PM
INSP-Sprinkler Rough-in8/20/20038/20/20038/20/2003PPART
DetailsTroy Cobbley
###-#### sprinkler piping is ok to cover on the third floor. I notified Bruce with Commercial fire that the sprinkler pendants located in the furnace rooms will need to be changed to 175 degrees 8/20/2003 4:11:09 PM
INSP-Sprinkler Rough-in/Hydro6/17/20036/17/20036/17/2003PPASS
DetailsTroy Cobbley
above ground hydro test is ok 6/17/2003 4:04:36 PM
INSP-Sprinkler Rough-in/Hydro6/16/20036/16/20036/16/2003PPASS
DetailsTroy Cobbley
bruce; Phone #: ###-#### Underground supply line hydro test is OK 6/16/2003 1:47:56 PM
INSP-Sprinkler Rough-in6/12/20036/12/20036/12/2003PPASS
DetailsTroy Cobbley
Bruce with Commercial Fire called to say that they installed the trace wire in the trench with the underground supply piping but that the contractor had started to bury the piping. He stated that he has digital pictures showning the wire in the trench. I stopped at the project and found all of the underground piping buried. I spoke to Sam Rogers and he stated that in this case the digital pictures will work for proof of trace wire
INSP-Supply line flush6/5/20036/6/20036/6/2003AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 6/5/2003 at 11:52:44 AM. Contact: ###-####. not a flush; UG wasn't complete and will need a recall to cover as wire wasn't in trench also; need 175 degree heads as shown on plans in HW room; need nail plates on vertical pipe on all second floor; couldn't check 3rd floor; resubmittal for modification to UG required to Bill A.; they are going to resubmit about drains shown on plans 6/6/2003 9:33:59 AM