INSP-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 | A | PASS |
Rick Jackson
|
|
|
This is Bobs # from Lea Electric; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 | P | FAIL |
Troy Cobbley
|
|
|
inspection not done since the main fire alarm system is not reporting correctly. I stopped the inspection 9/30/2003 3:50:56 PM
|
INSP-Final Inspection | 9/26/2003 | 9/26/2003 | 9/26/2003 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
INSP-Final Inspection | 9/17/2003 | 9/17/2003 | 9/17/2003 | P | FAIL |
Troy Cobbley
|
|
|
Provide breaker locks, provide breaker location in the nac panel, put the heater supply circuit on the facp circuit for supervision, provide placard per note #2, field inspector to verify with sam rogers cooling for the nac panel enclosures, provide fax of todays signal. There may be problems with what was send and how it was received 9/17/2003 4:17:20 PM
|