Permit Information
Permit NumberFIR03-00285
StatusFinaled
Name GIVENS PURSLEY LLP
Site Address 601 W BANNOCK ST
Project NameSPR DEMO GIVENS PURSLEY
Customer Number 
ePlanReview 
Description
(GIVENS PURSLEY LLP) This building is fire sprinklered to substitute for 1-hr fire-resistive construction. It would appear that no tenant is occupying this facility, since it was not addressed in the BLD review, and thus shall be considered as "VACANT." Fire sprinkler work is related to the demolition and reinstallation of fire sprinkler feed and cross-mains on the first floor (plan 1 of 3 attached). On completion of the new main installation, the existing lines will be connected. Also the remove existing drops (which leaves 2 layers of combustible area protection. This work is for the preparation of the remodel all 3 levels of an existing 34,500 square foot 3 story office building. The fire sprinkler system work shall be maintained in accordance with minimum requirements of NFPA 13-1999, complying with the IFC-2000 and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this permit, to provide witness of compliance verification of meeting minimum code. This permit is attached to building permit: BLD03-00342.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Conference8/12/20038/13/20038/13/2003PPASS
DetailsRick Jackson
1. Separated uses. Subsection2

2. test ord subsection 3