Permit Information
Permit NumberFIR03-00324
StatusFinaled
Name PEAK ALARM
Site Address 8385 W EMERALD
Project Namealm - WESTPARK
Customer Number 
ePlanReview 
Description
Existing Fire Alarm Panel will be replaced to accommodate seven (7) duct smoke detectors and sprinkler monitoring with two (2) antifreeze valves. 7/21/2003 - Plan Modification: eight (8) duct detectors total.

The associated building permit (BLD 03-0) is to remodel an existing 4700 sq.ft. tenant space by removing and relocating partitions, no new enclosed areas will be created, adding new interior tempered windows to existing office spaces, removing an existing exterior glass door and replacing with storefront glazing, Miscellaneous related interior finishes, Note this building is fully fire sprinklered any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (#pc308-03) rmh
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/22/20038/22/20038/22/2003PPASS
DetailsTroy Cobbley
michelle; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
INSP-Final Inspection8/6/20038/7/20038/7/2003PFAIL
DetailsTroy Cobbley
Phone #: ###-#### Repair the nac circuit, change text to supervisory for the remote tamper switches, provide verify zones labels 8/7/2003 2:46:26 PM
INSP-Final Inspection7/30/20037/31/20037/31/2003PFAIL
DetailsTroy Cobbley
could not perform test due to the apparent failure of the dialer module for the fire alarm pane. We did test standby battery requirements for the main facp and the power supply for the duct smoke detectors. The batteries are sized correctly 7/31/2003 12:54:04 PM
INSP-Conference7/25/20037/25/20037/25/2003PDONE
DetailsTroy Cobbley
spoke with the alarm technician about horn/strobe height placement, delay of pressure switch activation and inspectors test as installed by the fire sprinkler contractor 7/25/2003 3:54:25 PM
INSP-Sprinkler Rough-in/Hydro6/27/20036/27/20036/27/2003PPART
DetailsTroy Cobbley
russ; Phone #: ###-#### A temporary occupancy was given until the fire alarm system has been installed and approved. Temp was given with Dave Lokker's permission. All other items are OK