Permit NumberFIR03-00376
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 111 N CLOVERDALE RD
Project NameSPR UG FEDEX SHOP
Customer Number 
ePlanReview 
Description
To install 6" C-900 PVC under the footing, and out approximately 20'-0" east, then north approximately 137'0" to an existing (installed by others) 8" C-900 duel purpose supply, and 6" with D.I. C-50 up through the floor in a proposed new 10,600-ft/2, one story with mezzanine truck maintenance shop building. This building will be fully fire sprinklered. The fire sprinkler underground work shall comply with NFPA 13-1999, NFPA 24-1995 and the UFC-1997, attached review comment and conditions list, all as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-01206.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/24/200311/24/200311/24/2003APASS
DetailsTroy Cobbley
INSP-Supply line flush10/10/200310/10/200310/10/2003ANR
DetailsRick Jackson
attempted to flush but a limited amount of water flowed with valve wide open; checked plans and there is another valve upstream on the eastside of Cloverdale that may be partially closed 10/10/2003 4:03:28 PM
INSP-Sprinkler Rough-in/Hydro8/25/20038/25/20038/25/2003PPART
DetailsTroy Cobbley
sam; Phone #: ###-#### The remaining underground supply piping is ok to cover on the north building 8/25/2003 3:20:09 PM
INSP-Conference7/24/20037/24/20037/24/2003PPASS
DetailsTroy Cobbley
Inspection was for stub out of 5' and is ok to cover 7/24/2003 4:17:48 PM
INSP-Conference7/23/20037/23/20037/23/2003PCANC
DetailsTroy Cobbley
underground not ready 7/24/2003 7:37:03 AM