Permit NumberFIR03-00387
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 6213 N CLOVERDALE RD
Project NameSPR BRC-FREMONT BLDG
Customer Number 
ePlanReview 
Description
(DEBT REDUCTION SERVICES)(BRC FREMENT BLDG-SUITE 100) To modify, relocate and add fire sprinkler protection in the expansion of an existing 7,892-ft/2 to 10,359-ft/2 office, located at the south end of the building. This work is related to the removal of portions of an existing wall, the construction of new partitions, the installation of suspended ceiling system and the installation of an HVAC Unit. This building requires full fire sprinkler protection. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-01008.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Supply line flush8/21/20038/22/20038/22/2003APASS
DetailsTroy Cobbley
fire sprinkles finaled 8/22/2003 9:56:43 AM
INSP-Final Inspection8/21/20038/21/20038/21/2003PFAIL
DetailsTroy Cobbley
BRUCE; Phone #: ###-#### Trapeze hangers are to be secured against slippage per NFPA 13 8/21/2003 3:04:01 PM
INSP-Sprinkler Rough-in8/13/20038/13/20038/13/2003PPART
DetailsRick Jackson
bruce; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie straps oaky; armovers corrected; not hung from other piping; trapeze size increased okay and the one trapeze will not prevent slippage; still have heads in closet on one line; file room hasn't changed; need to verify tag and spare heads 8/13/2003 5:18:21 PM
INSP-Sprinkler Rough-in/Hydro8/11/20038/12/20038/12/2003PFAIL
DetailsTroy Cobbley
armovers to pendants exceed 24"(nfpa 13 6-2.3.4), sprinkler piping is hung from other sprinkler piping(nfpa 13 6-2.1.3), too many pendants supplied from a single drop(notes #12, I, J), pendant head spacing in the file room exceeds spacing allowed per review note #9, provide retaining straps for all top beam clamps, the trapeze hanger is sized incorrectly for the armover support, provide inspection tag on riser, provide nfpa 25 or verification the owner has it per note #19 8/13/2003 10:54:47 AM