INSP-Supply line flush | 8/21/2003 | 8/22/2003 | 8/22/2003 | A | PASS |
Troy Cobbley
|
|
|
fire sprinkles finaled 8/22/2003 9:56:43 AM
|
INSP-Final Inspection | 8/21/2003 | 8/21/2003 | 8/21/2003 | P | FAIL |
Troy Cobbley
|
|
|
BRUCE; Phone #: ###-#### Trapeze hangers are to be secured against slippage per NFPA 13 8/21/2003 3:04:01 PM
|
INSP-Sprinkler Rough-in | 8/13/2003 | 8/13/2003 | 8/13/2003 | P | PART |
Rick Jackson
|
|
|
bruce; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie straps oaky; armovers corrected; not hung from other piping; trapeze size increased okay and the one trapeze will not prevent slippage; still have heads in closet on one line; file room hasn't changed; need to verify tag and spare heads 8/13/2003 5:18:21 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/11/2003 | 8/12/2003 | 8/12/2003 | P | FAIL |
Troy Cobbley
|
|
|
armovers to pendants exceed 24"(nfpa 13 6-2.3.4), sprinkler piping is hung from other sprinkler piping(nfpa 13 6-2.1.3), too many pendants supplied from a single drop(notes #12, I, J), pendant head spacing in the file room exceeds spacing allowed per review note #9, provide retaining straps for all top beam clamps, the trapeze hanger is sized incorrectly for the armover support, provide inspection tag on riser, provide nfpa 25 or verification the owner has it per note #19 8/13/2003 10:54:47 AM
|