Permit Information
Permit NumberFIR03-00426
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 601 W BANNOCK ST
Project NameSPR GIVENS PURSLEY LLP
Customer Number 
ePlanReview 
Description
(GIVENS PURSLEY LLP) To modify and add fire sprinkler protection in the remodel of all 3 levels of an existing 34,500-ft/2, 3 story office building. Work is related basically due to 6 restrooms, the additions of interior nonbearing walls and suspended ceilings per drawings, engineering, and plan review conditions on file. This building is fire sprinklered to substitute for 1-hr fire-resistive construction. The fire sprinkler system shall comply with NFPA 13-1999 as regulated by the Fire Department. The fire sprinkler system work shall comply with UFC-1997, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. A demolition fire permit was issued under FIR03-00285. An underground fire permit was issued under FIR03-00408. This permit and the other fire permits are attached to building permit: BLD02-02853.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/30/20041/30/20041/30/2004APASS
DetailsRick Jackson
INSP-Final Inspection1/23/20041/23/20041/23/2004AFAIL
DetailsRick Jackson
need escutcheons on several sprinler heads; riser requires annual inspection; need sign on riser room door 1/23/2004 9:00:15 AM
INSP-Final Inspection12/5/200312/5/200312/5/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/5/2003 at 7:28:58 AM. Contact: ###-####. second floor (north side) okay to cover 12/5/2003 10:09:49 AM
INSP-Sprinkler Rough-in11/19/200311/19/200311/19/2003APART
DetailsRick Jackson
okay to cover area by central stair and curtain around stair 11/19/2003 11:22:57 AM
INSP-Sprinkler Rough-in/Hydro11/12/200311/13/200311/13/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 11/12/2003 at 12:43:18 PM. Contact: ###-####. okay to cover wide hallway just north of the stair that leads to third floor 11/13/2003 11:17:54 AM
INSP-Conference10/31/200311/3/200311/3/2003APART
DetailsRick Jackson
Larry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes met with Russ and Tim about combustible concealed spaces and options per NFPA 13 and for the designer to make sure it is calc'd okay 11/3/2003 9:39:21 AM
INSP-Final Inspection10/17/200310/17/200310/17/2003PPART
DetailsRick Jackson
need sign on outside bell; need calc sticker and blue inspection tag; need spare heads and box hung; remove tape and add escutcheons on several heads 10/17/2003 4:03:42 PM
INSP-Sprinkler Rough-in9/24/20039/24/20039/24/2003PPART
DetailsRick Jackson
russ; Phone #: ###-#### Internet Inspection Request from: Darla Downs areas okay to cover as shown on approved plans 9/24/2003 5:09:07 PM
INSP-Conference9/4/20039/4/20039/4/2003PPART
DetailsRick Jackson
russ; Phone #: ###-#### Internet Inspection Request from: Marc Lileks met with Russ and GC about minor changes in hallway due to ceiloing changes; dry sidewall to east canopy can be eliminated if it is noncombustible 9/4/2003 3:19:49 PM
INSP-Sprinkler Rough-in8/27/20038/27/20038/27/2003PPART
DetailsRick Jackson
russ; Phone #: ###-#### Internet Inspection Request from: Marc Lileks okay to cover 2nd floor restrooms only; minor modifications made in this area due to concrete wall - okay 8/27/2003 1:24:40 PM
INSP-Sprinkler Rough-in/Hydro8/20/20038/20/20038/20/2003PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 8/20/2003 at 9:39:21 AM. Contact: ###-####. okay to cover main hallway from main entrance to stair; still need some openings firestopped that lead to void area 8/20/2003 2:00:33 PM
INSP-Sprinkler Rough-in/Hydro8/12/20038/13/20038/13/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 8/12/2003 at 1:06:28 PM. Contact: ###-####. need to verify number of heads that can be off one inch' closet by stair head is too low; duct work obstructing heads in rooms north of stairs; okaty to cover areas highlighted on approved plans 8/13/2003 5:20:44 PM