Permit Information
Permit NumberFIR03-00448
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 1755 N LINDA VISTA LN
Project NameSPR DOGWOOD PLAZA
Customer Number 
ePlanReview 
Description
DOGWOOD PLAZA - UNDERGROUND * To install approximately 308' of 6", C-900, Class 50, PVC from the property line in Linda Vista Lane, west and up through the floor with a "In-Building Riser," within a specified location of the proposed 40,666-ft/2, 3 story, wood framed, 50 unit apartment structure. This building is fully fire sprinklered for area increase. The fire sprinkler underground work shall comply with NFPA 13-1999, NFPA 24-1995 and the UFC-1997, attached review comment and conditions list, all as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-00602
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/18/20046/21/20046/21/2004APASS
DetailsTroy Cobbley
All items on the correction notice corrected. 6/21/2004 1:24:20 PM
INSP-Final Inspection6/18/20046/18/20046/18/2004PPASS
DetailsTroy Cobbley
permit finaled 6/18/2004 3:39:43 PM
INSP-Final Inspection6/16/20046/17/20046/17/2004AFAIL
DetailsTroy Cobbley
provide correct canopies on all of the sprinkler pendants in the common areas on all floors. Per review note #3 lintels are to be provided above showers. No lintels have been provided. Sprinkler coverage is blocked by stub wall. Provide hydraulic test certificates. Provide additional heads for spare head cabinet (6 of each type) See note #42. 6/17/2004 3:10:36 PM
INSP-Final Inspection6/16/20046/16/20046/16/2004PFAIL
DetailsTroy Cobbley
Per the sprinkler fitter, he could not get the forward flush to pass. He will need to repipe drains. Room 203 sprinkler canopy is missing. Could not perform complete sprinkler inspection due to fire alarm inspection taking so long. 6/16/2004 3:42:43 PM
INSP-Sprinkler Rough-in/Hydro6/2/20046/3/20046/3/2004APASS
DetailsRick Jackson
24 hour air test okay 6/3/2004 11:02:50 AM
INSP-Sprinkler Rough-in6/1/20046/2/20046/2/2004APART
DetailsRick Jackson
Contact Brian - 24 Air Test; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Start air test 44 psi 6/2/2004 11:49:07 AM
INSP-Sprinkler Rough-in/Hydro6/1/20046/2/20046/2/2004APASS
DetailsRick Jackson
Contact - Brian -- Hydro Test; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Wet system hydro okay 6/2/2004 11:46:44 AM
INSP-Sprinkler Rough-in4/14/20044/14/20044/14/2004PPASS
DetailsTroy Cobbley
second floor corridor sprinkler piping is ok to cover 4/14/2004 4:36:31 PM
INSP-Sprinkler Rough-in4/8/20044/9/20044/9/2004APASS
DetailsTroy Cobbley
third floor corridor sprinkler piping is ok to cover 4/9/2004 9:30:59 AM
INSP-Sprinkler Rough-in4/7/20044/7/20044/7/2004PCANC
DetailsTroy Cobbley
Contact - Brian -- 3rd Floor Rough In; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro3/2/20043/4/20043/4/2004PPART
DetailsTroy Cobbley
Inspection was a hydro test. The hydro test passed but will need to be done again due to more sprinkler heads being cut into the piping as the project gets closer to completion 3/4/2004 3:44:08 PM
INSP-Sprinkler Rough-in/Hydro2/16/20042/17/20042/17/2004APART
DetailsTroy Cobbley
Sprinkler piping tie-ins from the second to the third floor are connected and ok for cover 2/17/2004 11:44:43 AM
INSP-Sprinkler Rough-in/Hydro2/12/20042/13/20042/13/2004APART
DetailsTroy Cobbley
1st and 2nd floor hydro test passed 2/13/2004 4:13:22 PM
INSP-Sprinkler Rough-in/Hydro2/11/20042/12/20042/12/2004PFAIL
DetailsTroy Cobbley
Sprinkler rough-in on the first floor is ok. Insulation inspection is needed before covering can be done.
Sprinkler rough-in on the second floor is ok except for hangers and supports are needed for the plastic piping mains. Also verification is needed that the piping changes to the rise up to the second floor do not adversely affect the hydraulic calculations 2/12/2004 3:24:10 PM
INSP-Sprinkler Rough-in/Hydro2/3/20042/4/20042/4/2004ACANC
DetailsTroy Cobbley
Inspection needed was a cover inspection. See fir03-00554 2/4/2004 8:59:18 AM
INSP-Sprinkler Rough-in1/30/20041/30/20041/30/2004PFAIL
DetailsTroy Cobbley
tenting not completed 1/30/2004 12:27:06 PM
INSP-Sprinkler Rough-in/Hydro1/29/20041/29/20041/29/2004PPART
DetailsTroy Cobbley
dry system hydro test and the underground hydro test are OK. Rough-in for the 3rd floor wet system is OK. Still needs a tenting inspection 1/29/2004 3:50:25 PM
INSP-Sprinkler Rough-in/Hydro1/27/20041/28/20041/28/2004AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/27/2004 at 1:32:24 PM. hydro on dry system failed; other items corrected for dry system 1/28/2004 12:18:21 PM
INSP-Sprinkler Rough-in1/21/20041/21/20041/21/2004PFAIL
DetailsTroy Cobbley
Inspection was for the rough-in on the attic dry system. Some hangers on the 4" main need to be attached to the top chord of the trusses and two EQ bracings need to be attached to the wall plate. Also need to provide signage showing location of the FDC 1/21/2004 3:03:54 PM
INSP-Sprinkler Rough-in/Hydro12/1/200312/2/200312/2/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/1/2003 at 2:45:36 PM. UG flush only okay 12/2/2003 8:35:11 AM
INSP-Sprinkler Rough-in/Hydro11/13/200311/14/200311/14/2003ADONE
DetailsTroy Cobbley
Inspection was actually a conference on sprinklers spaced off of obstructions in the nfpa 13 areas 11/14/2003 11:10:20 AM
INSP-Conference11/4/200311/5/200311/5/2003ADONE
DetailsTroy Cobbley
I spoke with the sprinkler fitter about sprinkler spacing from light fixtures. Per NFPA 13R the pendants need to be 3'6" to 4' from the fixtures. 11/5/2003 2:28:35 PM
INSP-Sprinkler Rough-in/Hydro8/26/20038/27/20038/27/2003APART
DetailsTroy Cobbley
Underground supply line is ok to cover. One section of the piping rises to within 4' of the existing grade but the excavator stated that another 10" of roadmix and then a layer of blacktop would be over it. I contacted Debest Fire and told them that I was giving an ok to cover and that if conduit was needed in the trench for PIV tamper they had better do it now. The control vavle location was not shown on the plans 8/27/2003 10:41:57 AM