Permit Information
Permit NumberFIR03-00450
StatusFinaled
Name IDAHO FIRE PROTECTION
Site Address 10356 W FAIRVIEW AVE Unit: 104
Project NameSPR VILLAGE SHOPPING CENTER
Customer Number 
ePlanReview 
Description
VILLAGE SHOPPING CENTER - NO TENANT - SUITE 104 * To replace, modify and relocated fire sprinkler protection for the remodel of an existing 5,883-ft/2, one story building. Three (3) separate "shell" tenant spaces are being created (Suite 100 - 2,951-ft/2, Suite 104 - 1,246-ft/2, Suite 105 - 1,600-ft/2). The specific tenants have NOT been disclosed. Separate tenant fire permits may be required for each tenant space before occupancy. Fire sprinkler work is related to 6 restrooms accessible to the disabled; interior nonbearing walls and suspended ceilings. A demolition permit (BLD03-01079) with an attached fire permit (FIR03-00406) was issued earlier. Fire permit was issued to get the building fire protection system functional prior to tenant work. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-01058.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/9/20044/9/20044/9/2004APASS
DetailsTroy Cobbley
fire sprinklers finaled
INSP-Sprinkler Rough-in/Hydro1/20/20041/21/20041/21/2004APART
DetailsTroy Cobbley
sprinkler piping is OK to cover 1/21/2004 10:25:30 AM
INSP-Sprinkler Rough-in/Hydro12/30/200312/30/200312/30/2003PPART
DetailsTroy Cobbley
Sprinkler piping is ok to cover in this tenant space. 12/30/2003 12:52:56 PM
INSP-Final Inspection12/19/200312/19/200312/19/2003PPART
DetailsTroy Cobbley
Temp occupancy given until the fire alarm and fire sprinklers are finaled
INSP-Sprinkler Rough-in12/16/200312/16/200312/16/2003PPART
DetailsTroy Cobbley
Pito test on the backflow preventer is OK. Alarm bell operates ok but I requested verification that the orfice matches the smallest sprinkler head orfice. Trapeze is ok on the main. Existing pipe sizing matches plans. Sprinkler pendants need to be changed to quick responce. Need signs on the riser, head wrench and NFPA 25. Still need alarm system completed. Need to double check review notes at final.
FIR-Aging Inspection11/18/200311/18/200311/18/2003 NR
DetailsTroy Cobbley
Stopped at the project. Could not get access but by looking through the window I could see that work is still in progress 11/19/2003 10:54:53 AM