INSP-Final Inspection | 9/22/2004 | 9/23/2004 | 9/23/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled 9/23/2004 12:35:14 PM
|
INSP-Final Inspection | 9/13/2004 | 9/17/2004 | 9/17/2004 | A | FAIL |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Alicia Pauley need outside alarm 9/17/2004 9:32:09 AM
|
INSP-Sprinkler Rough-in/Hydro | 9/30/2003 | 9/30/2003 | 9/30/2003 | P | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/30/2003 at 9:02:09 AM. family room okay to cover; submit as-builts with changes and any needed calc's 9/30/2003 2:20:22 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/22/2003 | 9/22/2003 | 9/22/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/22/2003 at 7:38:39 AM. Contact: ###-####. okay to cover tented areas; do not cover family room ceiling where there are beam obstructions and heads installed in bottom of beams; faxed replay back to Debest last Wednesday in reference to beam obstrcution with Sam Rogers concurrence that heads to be installed at ceiling and not the bottom of beams 9/22/2003 3:10:43 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/18/2003 | 9/19/2003 | 9/19/2003 | A | FAIL |
Troy Cobbley
|
|
|
The inspection was for tenting. Tenting on the first floor can be pushed off of the sprinkler piping in several locations. Not all tenting was inspected. All tenting to be looked at re-inspection 9/19/2003 11:17:11 AM
|
INSP-Sprinkler Rough-in/Hydro | 9/16/2003 | 9/17/2003 | 9/17/2003 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/16/2003 at 1:48:45 PM. Contact: ###-####. heads installed in soffits that are 12 inches - heads to be within 1-4 inches of ceiling and will require heads in pockets with calc's; need to verify 2 inch water meter; tenting not completed; minor changes made to piping including location of pipe to second floor; spare head box and test alarms; there is a control valve below backflow that is not allowed and can be relocated to shut off domestic 9/17/2003 2:24:37 PM
|