Permit Information
Permit NumberFIR03-00647
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 303 N ALLUMBAUGH ST
Project Namealm - INTERMOUNTAIN HOSPITAL
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm system. The new system is a required manual fire alarm system with complete automatic detection, sprinkler monitoring, HVAC shutdown, door release and fire/smoke damper release. This will occur over a four (4) phase, four (4) year upgrade process. (Approved by Dave Miller 11/12/2003).

The associated building permit (BLD 03-01809) is to upgrade the ceilings and door assemblies per Letter of Agreement on file to provide fully complying 1-hr. fire rated exit access corridors throughout per approved plans. To upgrade all applicable life safety components associated with the corridor upgrade as noted in plan review reports attached. PC03-430/drs (INTERMOUNTAIN HOSPITAL)(CORRIDOR UPGRADES)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/12/20057/12/20057/12/2005PPASS
DetailsTroy Cobbley
Permit finaled. Separate permits to be required for any future work. Phil Omis notified of this fact and agreed.
FIR-Aging Inspection7/11/20057/11/20057/12/2005 CANC
DetailsTroy Cobbley
INSP-Conference7/28/20047/28/20047/28/2004PDONE
DetailsTroy Cobbley
Fire alarm inspection for phases 1 and 2 are complete. The fire alarm contractor to resubmit drawings showing what work has been completed and then resubmit drawings for each additional phase that requires a building permit
INSP-Alarm Testing7/27/20047/27/20047/27/2004PPART
DetailsTroy Cobbley
The fire alarm in the south wing, phase II per the building permit is tested and complete. 7/27/2004 3:57:03 PM
INSP-Alarm Testing1/21/20041/21/20041/21/2004APART
DetailsTroy Cobbley
The items on he correction notice for the annex (north wing) have been completed. The fire alarm in this area is complete 1/21/2004 8:46:27 AM
INSP-Alarm Testing1/20/20041/20/20041/20/2004ACANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 1/20/2004 at 7:11:15 AM. Contact: ###-####.
INSP-Alarm Testing1/14/20041/14/20041/14/2004PPART
DetailsTroy Cobbley
The annex fire alarm system was tested. All fire alarm devices operated correctly except for one fire smoke damper in the corridor ceiling and the manual pull station at the nurses station. Also need to verify door locking requirements are met for an I-3 occupancy 1/14/2004 1:45:28 PM