Permit Information
Permit NumberFIR03-00673
StatusFinaled
Name PROTEX
Site Address 420 W MAIN ST
Project Namealm - VELTEX BUILDING-3RD FLR
Customer Number 
ePlanReview 
Description
To add HVAC shutdown, fire/smoke damper control and A/V coverage to an existing required manual fire alarm system that includes sprinkler monitoring, elevator recall/shutdown, HVAC shutdown, fire/smoke damper control and door release.

The associated building permit (BLD 03-00100) is to (SOURCE ONE)(VELTEX BLDG-3RD FLR) To finish an 11,000 sq.ft. full floor, office tenant with restrooms and hallways. Work to include installation of suspended ceiling, interior non-load bearing walls, HVAC system and duct work. All construction per the approved plan and attached comment list. NOTE: This building is fire sprinklered for story increase. MJP
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/19/20105/19/20105/21/2010APASS
DetailsForrest France
INSP-Final Inspection2/26/20072/27/20072/27/2007APART
DetailsForrest France
Need to verifiy items noted at last field inspection dated 1/12/04 per R. Jackson and inspect plan modification review details completed on 5/7/04.

INSP-Final Inspection1/12/20041/12/20041/12/2004PFAIL
DetailsRick Jackson
clean up NAC panel to remove spare wires; remove covers on smoke detectors 1/12/2004 3:23:44 PM
INSP-Final Inspection1/7/20041/7/20041/7/2004AFAIL
DetailsRick Jackson
notification needeed at room 302 and in new breakroom; lockout and repair circuit breaker; change descriptors for devices to indicatge third floor; need 7 amp hr batteries at NAC panel; need map 1/7/2004 11:01:03 AM