Permit Information
Permit NumberFIR03-00690
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 475 W PARKCENTER BLVD
Project NameDoubletree Club
Customer Number 
ePlanReview 
Description
To replace the existing fire alarm system to meet upgrade agreement between the owner and the Boise Fire Department. System is to include the installation of audible/visible devices in common areas, smoke detectors in common areas, duct smoke detectors for hvac shutdown and system smoke detectors with sounder bases in the guest rooms. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/20/20051/21/20051/21/2005PPASS
DetailsRick Jackson
CLIFF; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles All items corrected; final okay 1/21/2005 5:11:00 PM
INSP-Final Inspection12/27/200412/29/200412/29/2004PFAIL
DetailsRick Jackson
cliff; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Stopped inspection - room sounder bases didn't sound on general alarm; re-inspection fee will be added and must be paid prior to another inspection 12/29/2004 5:33:27 PM
INSP-Final Inspection11/4/200411/8/200411/8/2004ACANC
DetailsRick Jackson
###-#### Cliff Miller rescheduled for late afternoon per Cliff 11/8/2004 9:42:55 AM
INSP-Final Inspection11/8/200411/8/200411/8/2004PFAIL
DetailsRick Jackson
4:00 pm per Cliff Strobes in commonareas not working and sounder bases not working on general alarm; sounder base room detectors generate temporal tone with room detector in alarm 11/8/2004 5:12:13 PM
INSP-Final Inspection9/27/20049/29/20049/29/2004PFAIL
DetailsRick Jackson
as late as possible please///clifford; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Room sounder base detectors are not temporal tone on general alarm; strobes not sync'd; EOL voltage drop 20.5 on 6th floor circuit - all others are okay; need maps; mount remote annunciator permanently 9/30/2004 9:12:25 AM
INSP-Final Inspection8/31/20049/20/20049/20/2004AFAIL
DetailsRick Jackson
###-#### - cliff Need temporal tone on all sounder bases; sounder bases generate general alarm not supervisory as shown on matrix and drop mags for doors; elevator shunt not working; lockout for 120 volt breaker for shunt as it isn't supervised; all troubles okay on panel; need voltage drops on NAC's and test alarm notification; review the computer program for this system 9/20/2004 4:24:04 PM
INSP-Final Inspection8/31/20049/13/20049/13/2004AFAIL
DetailsRick Jackson
###-#### - cliff Need correct sized batteries for panel on 6th floor; need breaker location on all panels and lockout on breaker; point 45 not used as FACP area has two detectors in area; need descriptors for "modules" to indicate location; remote annunciator not installed permanently in front desk area; tested devices in hallways/closets on 2-6 floors; need to test kitchen hood; sprinkler devices, heat detectors in laundry, drops on NAC's as 14 gauge wire is used, penthouse pre-action troubles/alarm, duct detectors, and sounder base devices in rooms and notification in all areas 9/13/2004 11:46:31 AM
INSP-Conference8/26/20048/27/20048/27/2004APART
DetailsRick Jackson
cliff; Phone #: ###-#### Internet Inspection Request from: Annette Moore Met with Cliff about testing the system; will need to verify smoke detectors on wall in room; need to verify wire size/calc's for NAC's prior to testing 8/27/2004 11:03:16 AM
FIR-Aging Inspection3/4/20043/4/20043/4/2004 PASS
DetailsRick Jackson
Per Ken this is phased work that is scheduled for completion by 12/04. The first floor is in progress and the head end is completed. There is an agreement with BFD for the phasing. 3/4/2004 9:54:48 AM