Permit Information
Permit NumberFIR03-00692
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 120 N CURTIS RD
Project NameSPR BRICO OF IDAHO
Customer Number 
ePlanReview 
Description
To install a complete overhead fire sprinkler system in a 9,834-ft/2, one story Type VN fully building which has 3,062-ft/2, office/retail with 6,772-ft/2, warehouse space for storage of Class IIIB combustible products (Motor Oils, Transmission Fluid, etc.) outdoor storage of oil products in (6) 10,000 gallon steel tanks. The underground fire sprinkler supply main was permitted under FIR03-00627. Fire sprinklers used for area increase. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-00420.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/1/20043/2/20043/2/2004APASS
DetailsTroy Cobbley
fire sprinkler system finaled 3/2/2004 10:48:56 AM
INSP-Sprinkler Rough-in/Hydro2/23/20042/23/20042/23/2004PFAIL
DetailsTroy Cobbley
Anti-freeze valve must meet requirements of review note #24. Forward flush the backflow preventor. Provide flow switch with means for testing, valve supervision, and check valve for hose system. Resubmit plans per review notes
INSP-Sprinkler Rough-in/Hydro1/27/20041/28/20041/28/2004APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/27/2004 at 1:35:49 PM. Contact: ###-####. UG flush only - okay 1/28/2004 12:41:15 PM
INSP-Sprinkler Rough-in/Hydro1/28/20041/28/20041/28/2004PPART
DetailsRick Jackson
overhead hydro okay 1/28/2004 3:52:42 PM
INSP-Sprinkler Rough-in/Hydro1/26/20041/27/20041/27/2004PPART
DetailsTroy Cobbley
Office areas are ok to cover 1/27/2004 1:49:28 PM
INSP-Sprinkler Rough-in/Hydro1/12/20041/13/20041/13/2004APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/12/2004 at 2:25:09 PM. Contact: ###-####. okay to cover entyry and restrooms as items from previous inspection are okay 1/13/2004 10:03:13 AM
INSP-Sprinkler Rough-in/Hydro1/7/20041/9/20041/9/2004PFAIL
DetailsTroy Cobbley
Inspection was for the entry area and the two restrooms. The hangers in the entry area need to be attached to the top of the structure and the pendants exceed 3' vertically from the peak. The upright sprinkler heads over both of the restrooms are overspaced and will require additional upright coverage 1/9/2004 2:08:16 PM