Permit NumberFIR03-00698
StatusFinaled
Name TRI-STATE ELECTRIC
Site Address 7031 S EISENMAN RD
Project Namealm - POWERBAR
Customer Number 
ePlanReview 
Description
To add manual pull stations, one duct detector for HVAC shutdown and A/V notification appliances throughout the remodeled area to an existing required manual fire alarm system that includes sprinkler monitoring, fire/smoke damper control, HVAC shutdown and notification.

The associated building permit (BLD 03-01474) is to add 1685 sq. ft. of mezzanine for a lunch room and remodel 2299 sq. ft. of office, locker room and restrooms on the first floor in an unlimited area building per approved plans and attachments. Other items include new exterior doors and windows and a new exterior exit stairway. CZC03-00067. (POWERBAR)

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/5/20042/6/20042/6/2004APASS
DetailsRick Jackson
ben taylor; Phone #: ###-#### Internet Inspection Request from: Barbara Moore all items corrected 2/6/2004 8:28:02 AM
INSP-Final Inspection1/16/20041/16/20041/16/2004AFAIL
DetailsRick Jackson
duct detector not shutting AHU off; had to adjust strobes to proper CD in several areas; need updated map and record of completion 1/16/2004 11:05:19 AM