INSP-Final Inspection | 4/8/2004 | 4/9/2004 | 4/9/2004 | P | PASS |
Rick Jackson
|
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
INSP-Final Inspection | 4/7/2004 | 4/7/2004 | 4/7/2004 | P | CANC |
Troy Cobbley
|
|
|
Mike;please call first for access. thanks. Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
INSP-Final Inspection | 3/22/2004 | 3/23/2004 | 3/23/2004 | P | FAIL |
Troy Cobbley
|
|
|
I spoke with kevin filer (ansul ###-####) and he stated that the ansul system would not be listed unless it was used throughout the hood. Not just over the appliances. Contractor will need to modify the system per manufactures recommendations. 3/23/2004 3:20:41 PM
|
INSP-Final Inspection | 3/19/2004 | 3/22/2004 | 3/22/2004 | P | FAIL |
Troy Cobbley
|
|
|
provide signage at the hoods and at the manual pull stations. Inspector to verify with suppression system manufacturer listed use of suppression system on the Gaylord shelf hood. 3/22/2004 3:54:19 PM
|
FIR-Aging Inspection | 2/27/2004 | 2/27/2004 | 2/27/2004 | | FAIL |
Troy Cobbley
|
|
|
I met with the restraunt owner and left his a notice to have the permit finaled by March 19, 2004 or I would need to red tag the appliances beneath the hood in question. 3/5/2004 12:51:58 PM
|