Permit NumberFIR03-00765
StatusFinaled
Name GENERAL FIRE INC
Site Address 3662 S FINDLEY AVE
Project Namealm - FMLY CNTR-BLDG A1-stubs
Customer Number 
ePlanReview 
Description
To add two duct detectors for HVAC shutdown to an existing required sprinkler monitoring fire alarm system.

1/30/2004 - Revised scope, to monitor a cooking hood in the space. Per the inspection, the back flow preventer is not annunciated separately (see comment #1), the FACP has 8 zones and duct detectors are being relocated to provide a free zone for the cooking hood. The next Tenant Improvement the expectation will be that the back flow preventer will be separately annunciated as the IFC requires.

The associated building permit (BLD 03-02635) is to construct a 1,965 sq.ft. sports bar per approved plans. This space is at the south end of the building. Work to include, construction of two accessible restrooms, construction of partitions to divide kitchen restrooms and dinning areas, installation of related kitchen appliances, installation of a type-2 hood system above oven, new counters, sinks and miscellaneous related interior finishes. New Hvac system and lighting. This building is fully fire sprinkled for area increase, any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (pc#679-02) rmh (STUBS SPORTS PUB)(FAMILY CENTER-BLDG A1)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/12/20042/12/20042/12/2004PPASS
DetailsRick Jackson
jason; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
INSP-Final Inspection1/15/20041/15/20041/15/2004APASS
DetailsRick Jackson
The FACP has 8 zones and is full; the BFP tamper switches are not on a separate zone; the BFP has the wall PIV tamper on one side an OS and Y tamper on the other 1/15/2004 9:19:30 AM