INSP-Final Inspection | 6/17/2004 | 6/18/2004 | 6/18/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled. Alarm contractor is to attach some loose wire to building structural and I'll do a drive by next week to verify. 6/18/2004 1:04:07 PM
|
INSP-Final Inspection | 6/15/2004 | 6/15/2004 | 6/15/2004 | P | FAIL |
Troy Cobbley
|
|
|
NAC panel, circuit 3, on the second floor is in trouble (a/v's don't work). Need to verify batteries, end of line voltage drop and trouble signals on 2nd floor nac panel. Need to test heat detectors in attic. 6/15/2004 2:39:34 PM
|
INSP-Final Inspection | 5/28/2004 | 6/2/2004 | 6/2/2004 | P | FAIL |
Rick Jackson
|
|
|
1:00 pm Wrong candela installed - identified on plans; 18 amp hr bateries; add strobes in treadmill as shown on plans; identify trouble zones to monitoring company; will need to test trouble for secondary phone line and NAC's for voltage drops and NAC panels for troubles 6/2/2004 4:47:15 PM
|
INSP-Final Inspection | 5/28/2004 | 5/28/2004 | 5/28/2004 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 5/28/2004 at 10:20:24 AM. Contact: ###-####. Rrescheduled for 6/2/04 per Patrick 5/28/2004 12:59:49 PM
|
INSP-Final Inspection | 5/24/2004 | 5/24/2004 | 5/24/2004 | A | FAIL |
Troy Cobbley
|
|
|
Resubmitt drawings showing door holder changes, pull station changes and location changes for audio/visuals. Repair pull station. Get zone descriptions set up at monitoring company. Get phone lines set up as discussed (delete the separate dialer). No inspection was performed. All of the items listed above came to light during review of drawings at start of inspection
|
INSP-Final Inspection | 5/20/2004 | 5/21/2004 | 5/21/2004 | A | NR |
Troy Cobbley
|
|
|
contractor was not ready for inspection. To be rescheduled for Monday morning 5/21/2004 3:01:26 PM
|
INSP-Conference | 4/9/2004 | 4/9/2004 | 4/9/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 4/9/2004 at 8:47:30 AM. Contact: ###-####. Met with Patrick about some strobes needs in south aerobic room near vestibules 4/9/2004 2:52:07 PM
|