INSP-Sprinkler Rough-in/Hydro | 4/28/2004 | 4/29/2004 | 4/29/2004 | A | PASS |
Troy Cobbley
|
|
|
fire sprinklers finaled 4/29/2004 8:58:17 AM
|
INSP-Sprinkler Rough-in/Hydro | 4/21/2004 | 4/22/2004 | 4/22/2004 | A | FAIL |
Troy Cobbley
|
|
|
See approved plans for locations requiring attention. 4/22/2004 2:14:00 PM
|
INSP-Sprinkler Rough-in/Hydro | 4/20/2004 | 4/21/2004 | 4/21/2004 | A | FAIL |
Troy Cobbley
|
|
|
Resubmitted plans still do not match pipe sizing or layout of what has been installed. One area includes a remote area. See revised city plans for locations of problems. Upright heads in the attic along the east wall are spaced too far off of the wall since existing insulation does not fill the combustible space along the wall. Add insulation or sprinkler heads. There is a combustible cavity above the attic space that requires protection. Inspection stopped at locaton shown on plans. 4/21/2004 9:46:03 AM
|
INSP-Sprinkler Rough-in/Hydro | 4/13/2004 | 4/14/2004 | 4/14/2004 | A | PASS |
Troy Cobbley
|
|
|
Wet system and dry system hydro test passed 4/14/2004 11:19:38 AM
|
INSP-Sprinkler Rough-in/Hydro | 4/14/2004 | 4/14/2004 | 4/14/2004 | P | PART |
Troy Cobbley
|
|
|
Underground hydro test passed 4/14/2004 3:25:31 PM
|
INSP-Supply line flush | 4/8/2004 | 4/9/2004 | 4/9/2004 | A | PASS |
Troy Cobbley
|
|
|
Underground supply line flush OK 4/9/2004 9:26:58 AM
|
INSP-Sprinkler Rough-in | 4/7/2004 | 4/8/2004 | 4/8/2004 | P | PART |
Troy Cobbley
|
|
|
second floor sprinkler piping rough-in is ok .Other areas I looked at do not match plans. I spoke to Bill Alexander and he agreed with me that resubmittals are needed prior to a rough-in inspection. I left a message on Tom's phone and spoke to the on site sprinkler fitter about it. 4/8/2004 3:26:04 PM
|
INSP-Sprinkler Rough-in | 2/12/2004 | 2/12/2004 | 2/12/2004 | P | PART |
Troy Cobbley
|
|
|
underground supply piping is ok to cover. 2/12/2004 2:48:19 PM
|
INSP-Sprinkler Rough-in | 2/11/2004 | 2/11/2004 | 2/11/2004 | P | FAIL |
Troy Cobbley
|
|
|
need approved insulation detail on site prior to inspection 2/11/2004 2:45:22 PM
|