INSP-Final Inspection | 2/3/2005 | 2/4/2005 | 2/4/2005 | A | PASS |
Troy Cobbley
|
|
|
corrections made. Hood suppression system operated correctly. 2/4/2005 11:27:10 AM
|
INSP-Final Inspection | 1/14/2005 | 1/14/2005 | 1/14/2005 | P | FAIL |
Troy Cobbley
|
|
|
Relay now turns off toaster and leaves other appliances on. Needs fixed and reinspected. 1/14/2005 3:35:43 PM
|
INSP-Final Inspection | 12/30/2004 | 1/5/2005 | 1/5/2005 | A | FAIL |
Troy Cobbley
|
|
|
The toaster under the fryer hood did not lose power when the suppression system activated. All other items worked. Pull station locations are ok to remain as is. 1/5/2005 10:19:47 AM
|
INSP-Final Inspection | 3/25/2004 | 3/26/2004 | 3/26/2004 | A | CANC |
Rick Jackson
|
|
|
billy; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Requested 8 am; inspector has prior appointments at that time; will reschedule for next week 3/25/2004 1:47:47 PM
|