INSP-Final Inspection | 4/23/2004 | 4/23/2004 | 4/23/2004 | A | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled
|
INSP-Final Inspection | 4/19/2004 | 4/20/2004 | 4/20/2004 | P | FAIL |
Troy Cobbley
|
|
|
Provide spare heads in cabinet, chain and lock PIV, tag riser, provide NFPA 25 and test certificates 4/20/2004 4:09:39 PM
|
INSP-Sprinkler Rough-in/Hydro | 4/14/2004 | 4/15/2004 | 4/15/2004 | P | PASS |
Troy Cobbley
|
|
|
above ground and supply line hydro test is OK. Need forward flush and alarm test 4/15/2004 4:19:34 PM
|
INSP-Final Inspection | 4/12/2004 | 4/13/2004 | 4/13/2004 | A | CANC |
Troy Cobbley
|
|
|
not ready 4/13/2004 11:32:11 AM
|
INSP-Sprinkler Rough-in | 4/8/2004 | 4/8/2004 | 4/8/2004 | P | PART |
Troy Cobbley
|
|
|
sprinkler piping is ok to cover on the first floor but earth quake bracing still needs to be done. See plans for locations where upright heads are over spaced 4/8/2004 12:17:50 PM
|
INSP-Sprinkler Rough-in | 4/6/2004 | 4/6/2004 | 4/6/2004 | P | PART |
Troy Cobbley
|
|
|
2nd floor sprinkler rough-in is ok. Add earth quake bracing to main 10/15/2003 11:36:41 PM
|
INSP-Sprinkler Rough-in | 3/15/2004 | 3/15/2004 | 3/15/2004 | P | PART |
Troy Cobbley
|
|
|
Sprinklers under stairs are ok to cover 3/15/2004 2:51:44 PM
|
INSP-Supply line flush | 3/10/2004 | 3/11/2004 | 3/11/2004 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/10/2004 at 10:47:37 AM. Contact: ###-####. UG flush okay 3/11/2004 10:49:22 AM
|
INSP-Sprinkler Rough-in | 3/5/2004 | 3/5/2004 | 3/5/2004 | P | PART |
Troy Cobbley
|
|
|
Underground supply line is ok to cover 3/5/2004 3:03:33 PM
|