INSP-Final Inspection | 5/28/2004 | 5/28/2004 | 5/28/2004 | P | PASS |
Rick Jackson
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 5/21/2004 | 5/24/2004 | 5/24/2004 | P | FAIL |
Rick Jackson
|
|
|
Contact: Charles; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley remove tape from all heads; need spare heads; need blue annual inspection tag; install escutcheons/canopies; need overhead and underground certificates; outside bell not working with dry sprinkler flow 5/24/2004 4:32:02 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/20/2004 | 5/21/2004 | 5/21/2004 | A | FAIL |
Rick Jackson
|
|
|
Contact: Charles -- 200 lb test, please come after 10am; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley FDC hydro didn't hold pressure 5/21/2004 11:24:19 AM
|
INSP-Sprinkler Rough-in/Hydro | 5/19/2004 | 5/20/2004 | 5/20/2004 | A | PART |
Rick Jackson
|
|
|
Contact: Charles -- 2nd Floor Rough In; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Okay to cover second floor; need fire listing for compressor per plan review notes; need to hydro the FDC piping; ball drip to drain; complete bracing of dry test piping; need to forward flow backflow; alarms/tampers not ready; foam dry pendants in cooler 5/20/2004 10:32:26 AM
|
INSP-Sprinkler Rough-in/Hydro | 5/18/2004 | 5/19/2004 | 5/19/2004 | P | PART |
Rick Jackson
|
|
|
completion of 24 hr air test at 1 pm 40 psi Air test okay 5/19/2004 1:53:46 PM
|
INSP-Sprinkler Rough-in | 5/17/2004 | 5/18/2004 | 5/18/2004 | P | PART |
Rick Jackson
|
|
|
Contact - Charles -- 24 Hour Air Test; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Start of 24 hr air test on dry system 5/18/2004 2:59:23 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/17/2004 | 5/18/2004 | 5/18/2004 | P | PART |
Rick Jackson
|
|
|
Contact Charles -- 200 lb hydro; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Hydro on wet system only - okay 5/18/2004 1:26:03 PM
|
INSP-Sprinkler Rough-in | 5/13/2004 | 5/13/2004 | 5/13/2004 | A | PART |
Rick Jackson
|
|
|
Okay to cover 1st floor only 5/13/2004 10:00:04 AM
|
INSP-Supply line flush | 5/11/2004 | 5/13/2004 | 5/13/2004 | A | PASS |
Rick Jackson
|
|
|
Contact: Charles -- UG FLUSH; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley UG flush okay; still need hydro 5/13/2004 9:59:42 AM
|
INSP-Sprinkler Rough-in | 4/7/2004 | 4/8/2004 | 4/8/2004 | P | PART |
Troy Cobbley
|
|
|
Contact Charles; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
1st floor partial. OK to cover 2 rooms 1st floor (gypboard). Walked first floor, but too early for roughin.
|
INSP-Sprinkler Rough-in/Hydro | 3/19/2004 | 3/22/2004 | 3/22/2004 | P | PART |
Rick Jackson
|
|
|
Contact Mike - would like around 2 pm; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley UG stub-in from property line to just inside wall in basement okay to cover 3/22/2004 3:06:49 PM
|
INSP-Sprinkler Rough-in | 3/18/2004 | 3/19/2004 | 3/19/2004 | A | NR |
Rick Jackson
|
|
|
This is a cover inspection - contact mike -- would like at 12 noon.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Not ready; they will reschedule for 3/22/04 3/19/2004 1:39:41 PM
|