Permit Number | FIR04-00164 |
Status | Finaled |
Name |
DE BEST FIRE PROTECTION
|
Site Address |
413 N ALLUMBAUGH ST
|
Project Name | SPR UG SAGE MEDICAL |
Customer Number | |
ePlanReview | |
Description |
(Sage Medical) To install a approximately 72'-0" of 6", C-900 PVC, connected to an existing 6" fire service supply tapped in W. Morris Hill Lane, running south and around the east side, and down (south) to approximately even with a dedicated fire sprinkler riser control room then west under the footing with an Ames "In-Building Riser" and up through the concrete floor. Fire sprinkler control room appears to have an outside access door. This fire service supply is for protection of a new 10,080-ft/2, one story, Type VB, medical office SHELL building. Separate permits will be required for overhead systems and T.I.'s, BLD'S 04-00026, 04-00027, and 04-00028. The fire sprinklers have been used for area increase in relation to the construction. The fire sprinkler underground work shall comply with NFPA 13-1999, NFPA 24-1995 the IFC-2002, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD03-02970.
|