INSP-Final Inspection | 1/10/2005 | 1/11/2005 | 1/11/2005 | P | PASS |
Rick Jackson
|
|
|
Pull Stations at exits have been installed. Internet Inspection Request from: James Shilton Added pull stations okay 1/11/2005 1:48:48 PM
|
INSP-Final Inspection | 1/5/2005 | 1/6/2005 | 1/6/2005 | A | FAIL |
Rick Jackson
|
|
|
Internet Inspection Request from: James Shilton Need maunaul pulls at exits from dining areas; two duct detectors were added for the AHU 1/6/2005 11:13:46 AM
|
INSP-Sprinkler Rough-in/Hydro | 1/5/2005 | 1/6/2005 | 1/5/2005 | A | CANC |
Rick Jackson
|
|
|
Internet Inspection Request from: James Shilton Inspection cancelled from web by: James Shilton
|
INSP-Final Inspection | 10/26/2004 | 10/27/2004 | 10/27/2004 | P | PART |
Rick Jackson
|
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Dining/kitchen/storage area only okay; atrium and tunnel area not ready in Area A 10/27/2004 3:56:15 PM
|
INSP-Final Inspection | 7/15/2004 | 7/15/2004 | 7/15/2004 | P | PART |
Rick Jackson
|
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Area D okay - a pull station was added at the south exit that was not shown on plans 7/15/2004 1:51:37 PM
|
INSP-Final Inspection | 7/13/2004 | 7/14/2004 | 7/14/2004 | P | FAIL |
Rick Jackson
|
|
|
eric ###-#### Need manual pull at south exit; the detector addresses were increased by one; need disconnect for NAC panel 7/14/2004 3:39:47 PM
|