Permit Information
Permit NumberFIR04-00213
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 4614 W STATE ST
Project NameSPR DOLLAR STORE
Customer Number 
ePlanReview 
Description
(DOLLAR TREE STORE)(COLLISTER SHOPPING CENTER) To modify and add fire sprinklers removal of protection under mezzanine protection, in the remodel an existing 11,656 ft/2 space, for a Ordinary Group 2 retail new tenant occupancy. Fire sprinkler work is related to the construction of interior non-bearing walls to create the sales, stock room, office, two accessible restrooms & hallway areas. This building is fully sprinklered for allowable area increase. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-00222.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/22/20046/22/20046/22/2004PPASS
DetailsTroy Cobbley
Fire sprinkler permit finaled
INSP-Final Inspection5/7/20045/7/20045/7/2004PFAIL
DetailsTroy Cobbley
Insulation is still falling from the deck and blocking upright sprinkler heads
INSP-Final Inspection4/28/20044/28/20044/28/2004PFAIL
DetailsTroy Cobbley
Provide canopies on the sprinkler pendants. Insulation is still blocking sprinkler upright coverage in three locations. Provide annual inspection for the existing sprinkler system.
INSP-Final Inspection4/22/20044/23/20044/23/2004AFAIL
DetailsTroy Cobbley
Inspection was for covering of the sprinkler piping not a final. Sprinkler piping is ok to cover but insulation is still falling from the deck and blocking some of the sprinkler heads. Contractor can install ceiling tile. Insulation repair will be spot checked later. The existing fire alarm monitoring system has been disabled. I contacted the owner of the strip mall (Mike) and gave him until Monday 4-26-04 to repair the system. 4/23/2004 12:35:17 PM
INSP-Final Inspection4/20/20044/21/20044/21/2004PFAIL
DetailsTroy Cobbley
Provide the minimum 1" clearance between the upright deflector and the insulation, provide earthquake bracing on the existing sprinkler mains, pendants in the center of the retail space are overspaced. This inspection was for the retail space only. 4/21/2004 3:39:14 PM