Permit Information
Permit NumberFIR04-00251
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 8655 W FRANKLIN RD
Project NameSPR VIZIATO SPA/SALON
Customer Number 
ePlanReview 
Description
(VIZIATO SPA/SALON) To add, relocate and adjust fire sprinkler protection on an existing system installed in 3/95 for the remodel of an existing 3,392-ft/2, formerly used for the retail sales of mattresses space, for a new spa/salon. Fire sprinkler work is related to 2 shower/toilet rooms, interior nonbearing walls and some supports and millwork. This building is fire sprinklered for building area increase. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD03-02995.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/1/20052/1/20052/1/2005PPASS
DetailsRick Jackson
scott; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
INSP-Final Inspection1/25/20051/25/20051/25/2005PFAIL
DetailsTroy Cobbley
General contractor is going to provide verification that the anti-freeze loop has indeed been inspected by Grinnell. Some of the pendant heads need the dry wall mud removed before final. 1/25/2005 12:24:05 PM
INSP-Conference11/18/200411/18/200411/18/2004PDONE
DetailsTroy Cobbley
I spoke with the general contractor about the status of the fire alarm and fire sprinkler permits. He said he means to get the project finished up. Permit has expired on 10/25/2004. This will need to be resolve with bill alexander
INSP-Conference5/21/20045/21/20045/21/2004PDONE
DetailsTroy Cobbley
I spoke with representatives from Hawkin Smith about what I would be looking for as far as fire alarm requirements 5/21/2004 3:52:38 PM
INSP-Sprinkler Rough-in/Hydro5/10/20045/10/20045/10/2004AFAIL
DetailsTroy Cobbley
Provide access into the fire sprinkler riser room for verification of annual inspection tag on riser and verification of sprinkler monitoring. Provide verification that the anti-freeze loop located in this space has annual inspection. Provide electonic monitoring of the control valve for the anti-freeze loop by the fire alarm panel. This work will require a permit. Test the modified portion of the sprinkler system per review note #35. Sprinkler piping is ok to cover. 5/10/2004 9:54:38 AM