INSP-Final Inspection | 2/1/2005 | 2/1/2005 | 2/1/2005 | P | PASS |
Rick Jackson
|
|
|
scott; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
INSP-Final Inspection | 1/25/2005 | 1/25/2005 | 1/25/2005 | P | FAIL |
Troy Cobbley
|
|
|
General contractor is going to provide verification that the anti-freeze loop has indeed been inspected by Grinnell. Some of the pendant heads need the dry wall mud removed before final. 1/25/2005 12:24:05 PM
|
INSP-Conference | 11/18/2004 | 11/18/2004 | 11/18/2004 | P | DONE |
Troy Cobbley
|
|
|
I spoke with the general contractor about the status of the fire alarm and fire sprinkler permits. He said he means to get the project finished up. Permit has expired on 10/25/2004. This will need to be resolve with bill alexander
|
INSP-Conference | 5/21/2004 | 5/21/2004 | 5/21/2004 | P | DONE |
Troy Cobbley
|
|
|
I spoke with representatives from Hawkin Smith about what I would be looking for as far as fire alarm requirements 5/21/2004 3:52:38 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/10/2004 | 5/10/2004 | 5/10/2004 | A | FAIL |
Troy Cobbley
|
|
|
Provide access into the fire sprinkler riser room for verification of annual inspection tag on riser and verification of sprinkler monitoring. Provide verification that the anti-freeze loop located in this space has annual inspection. Provide electonic monitoring of the control valve for the anti-freeze loop by the fire alarm panel. This work will require a permit. Test the modified portion of the sprinkler system per review note #35. Sprinkler piping is ok to cover. 5/10/2004 9:54:38 AM
|