Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR04-00268
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 5680 W GAGE ST
Project NameSPR J & A ENTERPRISES
Customer Number 
ePlanReview 
Description
(J & A ENTERPRISES * DR. SONTAG) To modify by relocating and plugging existing fire sprinklers for the remodel of an existing 6,420-ft/2 building that is used as a medical office and for outpatient medical procedures. The medical gas system is existing and will be altered. Fie sprinkler work related to work is two 2 restrooms, interior nonbearing walls and some altered suspended ceilings. This fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-00495.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/6/20048/6/20048/6/2004PPASS
DetailsTroy Cobbley
Sprinkler permit finaled
INSP-Final Inspection7/30/20048/2/20048/2/2004PPART
DetailsRick Jackson
Contact: Brian ; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Okay to cover; will close out this permit at building final - need escutcheons and sprinkler is overdue annual inspection 8/2/2004 2:53:10 PM
INSP-Final Inspection7/20/20047/21/20047/21/2004PFAIL
DetailsTroy Cobbley
Upright sprinkler heads are overspaced in atleast three locations. See plans. Two pendant sprinkler heads are less than 6' apart. See plans. Atleast one armover exceeds 2'. See plans. Inspection was stopped and no other items looked at. These items appear to be existing conditions. Scope of work for the building permit encompasses the entire building therefore the entire sprinkler system shall meet code. Resubmitt plans showing all sprinkler piping, sizing and sprinkler head locations. Show modifications required to meet code. Do not install any more ceiling tile. 7/21/2004 3:35:13 PM
INSP-Sprinkler Rough-in6/16/20046/17/20046/17/2004APART
DetailsTroy Cobbley
sprinkler piping is ok to cover in procedure areas (two) and the two restrooms. See approved plans for areas. 6/17/2004 2:01:46 PM