Permit NumberFIR04-00270
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 9465 W EMERALD
Project NameSPR UG VIDEO EYE
Customer Number 
ePlanReview 
Description
Video Eye Corporation (Shell & Core-UG) - To install approximately 270'-0" of 6" C-900 PVC, connected in West Golden Trout property line United Water tap and routed into a fire sprinkler control room located near columns "3.5" and "A", in new 37,750-ft/2, two story, concrete tilt-up office/warehouse shell and core building. This is only an underground fire sprinkler supply for a shell and core permit. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 and the IFC-2000, attached review comment and conditions list, all as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-00300.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/1/200511/1/200511/1/2005PPASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection11/1/200511/1/200511/1/2005 PASS
DetailsTroy Cobbley
INSP-Supply line flush6/24/20056/27/20056/27/2005PPART
DetailsForrest France
Underground fire supply passed hydrostatic test, still need to witness UG flush.
INSP-Sprinkler Rough-in5/17/20045/18/20045/18/2004APART
DetailsRick Jackson
Contact - Mike Leiser -- UG Cover; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley UG okay to cover; will still need flush and hydro 5/18/2004 10:27:21 AM