Permit Information
Permit NumberFIR04-00350
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3138 S BOWN WAY
Project NameSPR BOWN CROSSING MRKT PL "A"
Customer Number 
ePlanReview 
Description
(BOWN CROSSING MRKT PL A) * To install a complete overhead fire sprinkler protection in a new 8,870-ft/2 two story shell combination retail, office and residential building. The 1st floor is 5,080-ft/2 and the 2nd floor is 3,790-ft/2. This building is fully fire sprinklered for code reduction and fire flow deficiencies. Separate permits with associated plans must be obtained and approved for each tenant space to be occupied. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work. The underground fire service supply was installed under FIR04-00083. This permit is attached to building permit: BLD03-02336.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/8/20058/8/20058/8/2005PPASS
DetailsForrest France
Fire sprinkler permit is finaled.
INSP-Sprinkler Rough-in4/21/20054/21/20054/21/2005PPASS
DetailsForrest France
Overhead fire sprinkler rough-in OK.
INSP-Final Inspection4/18/20054/18/20054/18/2005AFAIL
DetailsForrest France
Fire sprinkler rough-in inspection fail. Items need corrected include adding EQ brace 2nd floor south 2.5 in. main, upright too far off stair wall 2nd floor north, upright heads on two lines 2nd floor north are too low below deck.
INSP-Sprinkler Rough-in/Hydro4/18/20054/18/20054/18/2005PPASS
DetailsForrest France
Overhead hydro. test OK.
FIR-Aging Inspection9/15/20049/15/20049/15/2004 PASS
DetailsRick Jackson
Still under construction 9/15/2004 10:14:25 AM