(HYDE PARK MARKET & DELI - BOISE AIR TERMINAL - 2ND FLR) To install new pendant fore sprinklers in a new 631-ft/2 tenant space which includes a commercial kitchen and service counter, located next to the food court, within the new airport terminal building, on the 2nd floor within the security area (i.e. between the security check point and airplane loading). Fire sprinkler work is related to the installation of interior nonbearing walls, suspended ceilings and gypsum board soffits and bulkheads. A security grille is not equal to any occupancy separation from the terminal, which requires a minimum OH-1. This shell area was previously deigned for a minimum OH-2 under FIR02-00005. This building is fully fire sprinklered for fire area reasons. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01110.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro9/15/20049/16/20049/16/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 9/15/2004 at 3:12:35 PM. Contact: ###-####.