Permit Information
Permit NumberFIR04-00422
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 750 W MAIN
Project NameSPR CREPERY RESTAURANT
Customer Number 
ePlanReview 
Description
(SQUARE! - CREPERY RESTAURANT) To add 5 sprinklers for the remodel of an existing 2,520-ft/2, for a new restaurant tenant. This space is located on the first floor of an existing mixed-use (R-2, B, A-2, M) high-rise building. Fire sprinkler work is to include interior nonbearing walls, suspended gypsum board ceilings, a 10' x 16' overhead door, millwork, and finishes all per the approved drawings and the plan review report on file. This building is fire sprinklered because it is a high-rise. The fire protection work shall comply with the IFC 2000 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01053.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/2/20048/3/20048/3/2004APASS
DetailsRick Jackson
nick; Phone #: ###-#### Internet Inspection Request from: Annette Moore
INSP-Final Inspection7/29/20047/29/20047/29/2004PFAIL
DetailsRick Jackson
Kerry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes See rough-in inspection notes 7/29/2004 3:03:29 PM
INSP-Sprinkler Rough-in7/29/20047/29/20047/29/2004PPART
DetailsRick Jackson
Kerry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Installed as shown on plans however the Type I hood extinguishing system has been reduced to cover a small appliance at the north end of the hood leaving the rest of the area under the hood unsprinklered; heads are overspaced in the prep area from the Type I hood - maintain 130 sq ft 7/29/2004 3:03:03 PM