Permit Information
Permit NumberFIR04-00477
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 3430 N MAPLE GROVE RD
Project Namealm -King of Glory Luth Church
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system in an existing building and the new classroom addition. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown and notification throughout.

12/16/2004 - Revised scope of work: The FACP upgrade affects the entire building. There is a second floor that includes five classrooms with notification, pull stations at the exits and notification in the hallway.

The associated building permit (BLD 04-01255) is to construct a 6,028 s.f. one story, Type VB, fully fire sprinklered classroom addition and interior/exterior remodel to existing church structure per the approved plans and attachments. CUP03-00098 DRH03-00089 Fire sprinklers used for area. King of Glory Lutheran Church (Addition)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/4/20052/4/20052/4/2005APASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Alarm Testing1/27/20051/28/20051/28/2005AFAIL
DetailsRick Jackson
Let me know what time works for you so that I can know when to be there, and can schedule it with the General Contractor.; Phone #: ###-#### Internet Inspection Request from: Rick Groom Flow switch not working properly - cycles 1/28/2005 1:09:07 PM
INSP-Alarm Testing1/13/20051/14/20051/14/2005AFAIL
DetailsTroy Cobbley
Provide additional duct smoke detectors for units 4,5,6 and 8. See IMC 606.2.2. Test fire sprinkler devices. 1/14/2005 10:04:00 AM
FIR-Aging Inspection12/2/200412/2/200412/2/2004 NR
DetailsTroy Cobbley
Per Dave Maxwell work is in progress. He stated a plan modification was going to be subbmitted for the second floor. 12/2/2004 11:25:11 AM